BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B397292
Premises: 522 FULTON STREET BROOKLYN BIN: 3000466     Block: 161   Lot: 33
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 524 FULTON ST Census Tract:   37 Health Area:  2400
GROUND FLOOR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   HANOVER PLACE,    FLATBUSH AVENUE EXTENSION
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/19/2015 10:04 AM
Application Entered:   06/19/2015 Job Start Date:   06/19/2015
Last Change:   08/22/2025 Job End Date:   07/19/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     08/07/2015      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011440 Licensee Name: MARIO F CASTRO
Firm: 004009 Firm Name: POWER SURGE ELECTRIC, INC
Firm Phone: 718-276-9797  Firm Address: 122-20 MONTAUK STREET SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $497.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   REST
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAVAID S SYED
Owner Business Name: BURGER KING
Authorized Representative:  STAN PETERS
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  3/0
D. Over 250 MCM  1  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  100 AMP
C. 3 Phase Up to 225 AMPS  2  200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    48  35    15  48         
Buildings Total 48  35    15  48              
Total Units : 148 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 6 + New Meters 1 - Removed Meters 0 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 06/19/2015 Notice: 1 - FIRST NOTICE 08/17/2015
Power Issued: 06/19/2015 Response:  

Follow-Up:
Contractor's Comments:  REST. BURGER KING. EXISTING A/C

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B397292
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/09/2015 07/14/2015 HRB L (40) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW. NEED CONTRACTOR TO SHOW ALL WORK
 
(2) 07/23/2015 07/28/2015 GBZ P (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT AWARE OF INSPECTION NO SHOW
 
(3) 07/29/2015 08/04/2015 CJE N (0) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(4) 08/07/2015 08/17/2015 CCH V E (60) (11) Y
INSPECTION COMMENTS: WALK THROUGH NOT A FINAL

OBJECTION FOR APPLICATION #: B397292
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A FEEDERS TO METER FROM CON ED IN PNL FUSE 230.7
OPEN 08/07/2015 08/07/2015
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
ALL MIGB NOT BONDED
OPEN 08/07/2015 08/07/2015
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
WATER GROUND NOT TO NEUTRAL TERMINAL
OPEN 08/07/2015 08/07/2015
 
004 (999) OTHER
B RACEWAY TO WATER GROUND NOT CONTINOUS 250.64
OPEN 08/07/2015 08/07/2015
 
005 ( 19) DEFECTIVE WIRING IS IN USE
TV ON CEILING OUTLETS INSIDE CEILING
OPEN 08/07/2015 08/07/2015
 
006 (999) OTHER
C SUPP GROUND NOT TO BUILDING STEEL 250.52
OPEN 08/07/2015 08/07/2015
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUND WIRE NOT PROPERLY INSTALL IN PNLS
OPEN 08/07/2015 08/07/2015
 
008 (999) OTHER
D PANEL USE AS RACEWAY BSMT 1ST FL 312.8
OPEN 08/07/2015 08/07/2015
 
009 ( 42) BUSHINGS ARE MISSING OR LOOSE
EMT CONNECTOR MISSING BUSHING
OPEN 08/07/2015 08/07/2015
 
010 (999) OTHER
E CIRCUIT NOT GROUP THROUGHOUT 300.20
OPEN 08/07/2015 08/07/2015
 
011 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
NO DIS FOR WALK IN FRIDGE
OPEN 08/07/2015 08/07/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order