DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B395410
Premises: 53 BRIDGE STREET BROOKLYN BIN: 3335871     Block: 42   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 53 BRIDGE ST Census Tract:   21 Health Area:  1000
METER ROOM, FLOORS 2-8 Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   WATER STREET,    FRONT STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/08/2015 10:25 AM
Application Entered:   05/08/2015 Job Start Date:   05/08/2015
Last Change:   08/22/2025 Job End Date:   12/31/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     10/09/2020      
Field Disp:   H - NO PROGRESS ON JOB
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 011101 Licensee Name: JOSHUA GUTTMAN
Firm: 001557 Firm Name: ZEV ELECTRIC CORP.
Firm Phone: 718-522-1267  Firm Address: 202 PLYMOUTH STREET 1ST FLR BROOKLYN NY 11201 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JACK GUTTMAN
Owner Business Name: 53 BRIDGE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  72  4- #2 RISERS
B. Over #2 to 1/0  1  3- #1/0 FIRE PUMP
C. Over 1/0 to 250 MCM  12  4- #3/0 METER BNKS
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  72  12 POSITION
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL              40         
002    48  96    24  48             
003    48  96    24  48             
004    48  96    24  48             
005    48  96    24  48             
006    48  96    24  48             
007    48  96    24  48             
008    16    72         
Buildings Total 296  592    148  296     43           
Total Units : 1375 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 72 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 05/08/2015 Notice: C - CALL TO OFFICE 10/13/2020
Power Issued: 05/08/2015 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B395410
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/11/2019 12/11/2019 CJH N (33) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 06/16/2020 06/16/2020 JGX V (52) (11)
INSPECTION COMMENTS: INCOMPLETE INSPECTION. CONTACT - EPHRAIM HERSKOVITS (347)219-3109.
 
(3) 08/21/2020 08/21/2020 JGX J X (41) (0) Y
INSPECTION COMMENTS: INCOMPLETE INSPECTION. CONTACT - EPHRAIM HERSKOVITS (347)219-3109. 4 OF 11 OBJECTIONS (#2, #3, #4, AND #5) ARE RESOLVED. INSPECTOR UNABLE TO RESOLVE IN SYSTEM. ALL OTHERS REMAIN OPEN. A/C SYSTEMS STILL NOT INSPECTED. GROUNDING AT EMERG/EXIT LIGHTS TO BE VERIFIED.
 
(4) 10/09/2020 10/13/2020 GYM H X (90) (0) Y
INSPECTION COMMENTS: INSPECTED FIXTURES ONLY. . CONTRACTOR NO SHOW.

OBJECTION FOR APPLICATION #: B395410
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(FLOOR: 001)NO EGC'S PROVIDED AT CHANDELIERS AND SCONCES. ART. 410.46
OPEN 06/16/2020 06/16/2020
 
002 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(FLOOR: 004)RM 401 - DEFECTIVE BX TO WATER HEATER AT SINK - SOUTH WALL. AMEND110.2.A
OPEN 06/16/2020 06/16/2020
 
003 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(FLOOR: 004) DEFECTIVE EXIT LIGHT AT HALLWAY. AMEND 110.2.A
OPEN 06/16/2020 06/16/2020
 
004 (329) OPENINGS TO BE SEALED
(FLOOR: 004) RM 401 - OPEN KO'S AT 1900 BOX. ART. 110.12.A
OPEN 06/16/2020 06/16/2020
 
005 ( 61) INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS
(FLOOR: 004) SETBACK AT RECEPS IN SHEETROCK. ART. 314.20
OPEN 06/16/2020 06/16/2020
 
006 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 007)RM 711 - EGC TERMINATED AT NEUTRAL IN PANEL. ART. 250.24.A.5
OPEN 06/16/2020 06/16/2020
 
007 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 007)RM 711 - EGC NOT INSTALLED AT QUAD NEAR DOOR. ART. 250.146
OPEN 06/16/2020 06/16/2020
 
008 ( 27) ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS
(FLOOR: 007)RM 711 - NO ANTI-SHORT BUSHING AT BX IN PANEL. ART. 320.40
OPEN 06/16/2020 06/16/2020
 
009 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
(FLOOR: 007)RM 711 - EGC NOT TERMINATED TO BOX AT RECEP AT NORTH WALL. ART.250.118
OPEN 06/16/2020 06/16/2020
 
010 ( 61) INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS
(FLOOR: 007) RM 711 - SETBACK AT QUAD NEAR DOOR. ART. 314.20
OPEN 06/16/2020 06/16/2020
 
011 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ALL FLOORS)EGC'S NOT TERMINATED TO BOXES AT EXIT LIGHTS. ART. 250.118
OPEN 06/16/2020 06/16/2020