| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400 AMP |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
10 |
4/3 |
| B. Over #2 to 1/0 |
2 |
3/0 |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
10 |
20-40 |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER 1ST FL PANEL ON STAIR 240.B2 |
RSLV |
08/25/2015 |
08/25/2015 |
09/11/2015 |
| |
| 002 |
( 10) |
BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE ALL STOVE WIRE WITH#12 OUTLET |
RSLV |
08/25/2015 |
08/25/2015 |
09/11/2015 |
| |
| 003 |
(999) |
OTHER ALL STOVE NEUTRAL BONDED BEHIND 250.24 |
RSLV |
08/25/2015 |
08/25/2015 |
09/11/2015 |
| |
| 004 |
(999) |
OTHER UTILITY BAR NOT ACCESSIBLE 314.29 |
RSLV |
08/25/2015 |
08/25/2015 |
09/11/2015 |
| |
| 005 |
( 19) |
DEFECTIVE WIRING IS IN USE NO FIXTURES FRONT OF BUILDING |
RSLV |
08/25/2015 |
08/25/2015 |
09/11/2015 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED GROUNDING TERMINAL IN PANELS NEED 2 SCREWS |
RSLV |
08/25/2015 |
08/25/2015 |
09/11/2015 |
| |
| 007 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED GROUNDING TERMINAL NOT FROM PLP |
RSLV |
08/25/2015 |
08/25/2015 |
09/11/2015 |
| |
| 008 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER ALUM SER SW CHASE NIPPLE USE |
RSLV |
09/11/2015 |
09/11/2015 |
10/21/2015 |
| |
| 009 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED GROUNDING TERMINAL IN PANELS NEED 2 SCREWS |
RSLV |
09/11/2015 |
09/11/2015 |
10/21/2015 |