Electrical Application Details for App #: B393928
Premises: 310 LAFAYETTE AVENUE BROOKLYN BIN: 3055546     Block: 1947   Lot: 28
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 310 LAFAYETTE AV Census Tract:   197 Health Area:  1200
BASEMENT, 1ST, 2ND AND 3RD Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   302
DOB Cross Street(s):   ST JAMES PLACE,    GRAND AVENUE
Status:   C - JOB IS SIGNED OFF 07/22/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/03/2015 2:53 PM
Application Entered:   04/03/2015 Job Start Date:   04/03/2015
Last Change:   07/22/2016 Job End Date:   07/02/2015
Appointment Status:   
Last Inspection By:   BANYA, E       On     06/21/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010397 Licensee Name: WILLIAM MORALES
Firm: 000930 Firm Name: MANDA ELECTRIC COMPANY
Firm Phone: 917-687-7164  Firm Address: 900 WYCKOFF AVENUE BROOKLYN NY 11237 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $125.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TOM NIGRELLI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  125 AMP 20 CKTS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    12  12             
001    17  17  17             
002    19  19  19             
003    18  20  18             
Buildings Total 66  61  29  66                
Total Units : 230 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/17/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING 2 PANELS, SWITCHES, OUTLETS, FIXTURES AND SMOKE/CO DETECTORS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B393928
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/02/2015 12/03/2015 CJH V (60) (10) Y
INSPECTION COMMENTS: ROOF AC UNITS NOT INSPECTED
 
(2) 03/23/2016 03/24/2016 PAT V Y (60) (2)
INSPECTION COMMENTS: FAIL
 
(3) 05/17/2016 05/17/2016 CCH V Y (80) (4)
INSPECTION COMMENTS: JOB FAIL
 
(4) 06/21/2016 06/22/2016 EBA C R (40) (0)
INSPECTION COMMENTS: VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B393928
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(ALL FLOORS) CELLAR RECEPTACLE OUTLETS THROUGHOUT 250.146
RSLV 12/02/2015 12/02/2015 05/17/2016
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) 1ST FL PNL END 250.112
RSLV 12/02/2015 12/02/2015 05/17/2016
 
003 (999) OTHER
(ALL FLOORS) 1ST FL CKT NOT GROUPED 201.40
RSLV 12/02/2015 12/02/2015 06/21/2016
 
004 (999) OTHER
(ALL FLOORS)THROUGHOUT ALL KITCHEN COUNTER TOP RECEPTACLE OUTLETS CKT SHARE WITH DISH WASHER HOOD, GABBAGE, DISPOSAL 201.52
RSLV 12/02/2015 12/02/2015 03/23/2016
 
005 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(ALL FLOORS) 1ST FL KITCHEN COUNTER TOP GFCI 110.2
RSLV 12/02/2015 12/02/2015 05/17/2016
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) 1ST FL REAR NO GFCI 210.8
RSLV 12/02/2015 12/02/2015 03/23/2016
 
007 (999) OTHER
(ALL FLOORS) 1ST FL REAR RECEPTACLE OUTLET NOT WR 406.8
RSLV 12/02/2015 12/02/2015 03/23/2016
 
008 (999) OTHER
(ALL FLOORS) 1ST FL REAR BUBBLE COVER NOT PROVIDED 406.8
RSLV 12/02/2015 12/02/2015 03/23/2016
 
009 (220) DOUBLE LUGGING IN SERVICE SWITCH
(ALL FLOORS) 2ND FL TWO CONDUCTOR ONE BRAKER 110.14
RSLV 12/02/2015 12/02/2015 03/23/2016
 
010 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) 3RD FL PNL KO 110.12
RSLV 12/02/2015 12/02/2015 03/23/2016
 
011 (185) MULTIPLE SOURCE DISCONNECTS NOT GROUPED/IDENTIFIED
(FLOOR: 001)NO DISCONNECT SWITCH FOR ELECTRIC COMBO GAS OVEN ART 620.21(A)
RSLV 03/23/2016 03/23/2016 05/17/2016
 
012 ( 53) GFCI HAS NOT BEEN PROVIDED
(ROOF) NO GFCI 210.8
RSLV 03/23/2016 03/23/2016 05/17/2016
 
013 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 001) ISLAND IN KITCHEN
RSLV 05/17/2016 05/17/2016 06/21/2016
 
014 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 001) #14 USE IN PANEL
RSLV 05/17/2016 05/17/2016 06/21/2016
 
015 (999) OTHER
(FLOOR: 001) CIRCUITS NOT GROUP 300.20
RSLV 05/17/2016 05/17/2016 06/21/2016
 
016 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(CELLAR) ALL GROUND WIRE IN OUTLET BOXES
RSLV 05/17/2016 05/17/2016 06/21/2016