| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
2 |
125 AMP 20 CKTS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (ALL FLOORS) CELLAR RECEPTACLE OUTLETS THROUGHOUT 250.146 |
RSLV |
12/02/2015 |
12/02/2015 |
05/17/2016 |
| |
| 002 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS) 1ST FL PNL END 250.112 |
RSLV |
12/02/2015 |
12/02/2015 |
05/17/2016 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS) 1ST FL CKT NOT GROUPED 201.40 |
RSLV |
12/02/2015 |
12/02/2015 |
06/21/2016 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)THROUGHOUT ALL KITCHEN COUNTER TOP RECEPTACLE OUTLETS CKT SHARE WITH DISH WASHER HOOD, GABBAGE, DISPOSAL 201.52 |
RSLV |
12/02/2015 |
12/02/2015 |
03/23/2016 |
| |
| 005 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (ALL FLOORS) 1ST FL KITCHEN COUNTER TOP GFCI 110.2 |
RSLV |
12/02/2015 |
12/02/2015 |
05/17/2016 |
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS) 1ST FL REAR NO GFCI 210.8 |
RSLV |
12/02/2015 |
12/02/2015 |
03/23/2016 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) 1ST FL REAR RECEPTACLE OUTLET NOT WR 406.8 |
RSLV |
12/02/2015 |
12/02/2015 |
03/23/2016 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS) 1ST FL REAR BUBBLE COVER NOT PROVIDED 406.8 |
RSLV |
12/02/2015 |
12/02/2015 |
03/23/2016 |
| |
| 009 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH (ALL FLOORS) 2ND FL TWO CONDUCTOR ONE BRAKER 110.14 |
RSLV |
12/02/2015 |
12/02/2015 |
03/23/2016 |
| |
| 010 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) 3RD FL PNL KO 110.12 |
RSLV |
12/02/2015 |
12/02/2015 |
03/23/2016 |
| |
| 011 |
(185) |
MULTIPLE SOURCE DISCONNECTS NOT GROUPED/IDENTIFIED (FLOOR: 001)NO DISCONNECT SWITCH FOR ELECTRIC COMBO GAS OVEN ART 620.21(A) |
RSLV |
03/23/2016 |
03/23/2016 |
05/17/2016 |
| |
| 012 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ROOF) NO GFCI 210.8 |
RSLV |
03/23/2016 |
03/23/2016 |
05/17/2016 |
| |
| 013 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 001) ISLAND IN KITCHEN |
RSLV |
05/17/2016 |
05/17/2016 |
06/21/2016 |
| |
| 014 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 001) #14 USE IN PANEL |
RSLV |
05/17/2016 |
05/17/2016 |
06/21/2016 |
| |
| 015 |
(999) |
OTHER (FLOOR: 001) CIRCUITS NOT GROUP 300.20 |
RSLV |
05/17/2016 |
05/17/2016 |
06/21/2016 |
| |
| 016 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (CELLAR) ALL GROUND WIRE IN OUTLET BOXES |
RSLV |
05/17/2016 |
05/17/2016 |
06/21/2016 |