| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
200AMPS |
| C. 201 Up to 600 AMPS |
3 |
600AMPS |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
4 |
3/O |
| D. Over 250 MCM |
8 |
300 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
200AMP |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 12) |
SERVICE CONDUCTORS ARE NOT OF THE PROPER SIZE PLP SRVC/SW 2/0 FUSE AT 200A |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 002 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE DOCTOR'S OFFICE SRVC/SW NEUTRAL NOT BONDED |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 003 |
(228) |
USING PANEL AS A RACEWAY PLP PANEL |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 004 |
(999) |
OTHER PLP PANEL CIRCUITS NOT GROUPED 210.4D |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 005 |
(999) |
OTHER PLP PANEL MULTIWIRE CIRCUITS REQ'D HANDLE TIE 210.4B |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED A+B SERVICE RECEPTACLE |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 007 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH DOCTOR'S OFFICE 200A DISC/SW NEUTRAL |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 008 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE PLP PANEL #12 AWG ON 60A 2 POLE BRKR |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 009 |
(999) |
OTHER PLP PANEL 2 POLE 60A NOT LISTED 110.3B |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 010 |
(228) |
USING PANEL AS A RACEWAY PLP PANEL |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |
| |
| 011 |
(999) |
OTHER NO SIGNS PROVIDED FOR ROOMS A,B+C 110.2C |
RSLV |
07/01/2015 |
07/01/2015 |
09/24/2015 |