BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B392878
Premises: 877 BAY RIDGE AVENUE BROOKLYN BIN: 3143013     Block: 5770   Lot: 45
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 877 69 ST Census Tract:   128.01 Health Area:  8020
SIDEWALK SHED Admin Area:   B - BROOKLYN Inspection Area:   M
BROOKLYN, NY 11220 Community Board:   310
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/12/2015 10:34 AM
Application Entered:   03/12/2015 Job Start Date:   03/17/2015
Last Change:   08/22/2025 Job End Date:   12/02/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     08/26/2015      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 010377 Licensee Name: MICHAEL BAPTISTE
Firm: 002413 Firm Name: WCK ELECTRIC CORP.
Firm Phone: 917-909-1048  Firm Address: 1274 PROSPECT AVENUE BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $45.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: J&G GENERAL CONTRACTING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    12    14             
Buildings Total 12    14                
Total Units : 30 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/15/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  WIRING FOR SIDE WALK SHED

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B392878
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/26/2015 09/15/2015 JTE A (30) (5) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: B392878
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (140) TYPE NM CABLE USED FOR SIDEWALK SHED
USING ROMEX TO FEED SHED LIGHTS
OPEN 08/26/2015 08/26/2015
 
002 ( 19) DEFECTIVE WIRING IS IN USE
ROMEX BEING SPLICED WITH UNGROUNDED PIG TAIL
OPEN 08/26/2015 08/26/2015
 
003 (999) OTHER
SHED BEING FED B OUTLET INSIDE ELECTRICAL RM NOT ON ITS OWN CIRCUIT590.4(C)
OPEN 08/26/2015 08/26/2015
 
004 (323) GFCI NOT PROVIDED FOR TEMP WIRING
NO GFCI RECEPTACLE PROVIDED FOR SHED
OPEN 08/26/2015 08/26/2015
 
005 (168) EQUIPMENT IS NOT PROPERLY GROUNDED
SIDE WALK SHED LIGHTS NOT PROPERLY GROUNDED
OPEN 08/26/2015 08/26/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.