| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
3 |
100 AMP |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
3#2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
3 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
2 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS) BSMT-G.E.C. NOT CONTINUOUS 250.64(C) |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) BSMT-PANEL DIRECTORY NOT PROVIDED 408.4 |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS) BSMT-E.G.C NOT PROVIDED FOR FMC FROM SER SW 348.60 |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS) 2ND FL-DIS SW NOT PROVIDED FOR SPLIT UNITS |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) 2ND &3RD FL-SMOKE DETECTORS NOT AFCI PROTECTED 210.12 |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)2ND & 3RD FL-PANELS MULTIWIRE CKT'S NOT SIMULTANEOUSLY TRIP 210.4 |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS)ERD FL-FLEXIBLE CORDS USED AS PERMANENT WIRING FOR UNDER COUNTER LIGHTS 400.8 |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS) ROOF-DIS SW FOR AC UNITS NOT LABEL 404, 110.22 |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS) ROOF-EGC NOT PROVIDED FOR LFMC 350.60 |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS)ROOF-RECEPTACLE COVER NOT SUITABLE FOR WET LOCATION 406.8 |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS)ALL PANELS-INSULATED FITTING NOT PROVIDED FOR #4 OR LARGER 300.4(G) |
RSLV |
11/19/2015 |
11/19/2015 |
02/19/2016 |