BIS Menu  |  Complaint  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B391581
Premises: 1901 EMMONS AVENUE BROOKLYN BIN: 3326914     Block: 8775   Lot: 41
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1901 EMMONS AV Census Tract:   608 Health Area:  8721
BASTMENT AND ELEVATOR PIT Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11235 Community Board:   315
DOB Cross Street(s):   EAST 19 STREET,    OCEAN AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/03/2015 3:22 PM
Application Entered:   02/03/2015 Job Start Date:   02/03/2015
Last Change:   08/22/2025 Job End Date:   07/03/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     11/03/2016      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010939 Licensee Name: MICHAEL L ALPHONSE
Firm: 002249 Firm Name: BESTCO GENERAL ELEC. MAIN
Firm Phone: 718-324-5582  Firm Address: 922 EAST 233RD STREET BRONX NY 10466 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
Total Fee:  $187.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   COMMERCIAL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEVE PAPPAS
Owner Business Name: LENDY/ SMANAGMERT CORP.
Authorized Representative:  STEVE PAPPAS
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4 #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  SET 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  100AMP.- 3-PHASE
C. 3 Phase Up to 225 AMPS  1  200AMP. 3- PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                         
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 07/26/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALLING 1-200AMP.PANEL 42CKT.AND 1-100AMP.24 CKT.PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B391581
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/29/2015 05/05/2015 JTE J (40) (0) Y
INSPECTION COMMENTS: REP ON SITE CLAIMS THIS CONT IS ONLY RESPONSIBLE FOR PROVIDING A 200A PANEL. 100A DISC/SW BUT NOT FOR ELEVATOR/NOT A FINAL
 
(2) 03/16/2016 03/16/2016 WYF N (49) (0) Y
INSPECTION COMMENTS: SEWAGE FLOOD IN BASEMENT NO ACCESS
 
(3) 04/25/2016 04/27/2016 EBA N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(4) 05/27/2016 05/31/2016 DAH N (16) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(5) 07/06/2016 07/08/2016 EBA N (35) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(6) 07/18/2016 07/26/2016 BUR V (55) (9)
INSPECTION COMMENTS: CONTRACTOR STATED NO WORK WAS DONE ON ELEVATOR WIRING
 
(7) 11/03/2016 11/04/2016 EID J Y (73) (0)
INSPECTION COMMENTS: INSPECTION COMPLETED. EXISTING OPEN OBJ.

OBJECTION FOR APPLICATION #: B391581
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR) NO ARC FLASH STICKERS PROVIDED ON EQUIPMENT
RSLV 07/18/2016 07/18/2016 11/03/2016
 
002 (999) OTHER
(CELLAR)EQUIPMENT GROUNDING CONDUCTOR DOUBLED LUGGED IN JUNCTION BOX
RSLV 07/18/2016 07/18/2016 11/03/2016
 
003 (999) OTHER
(CELLAR) NO WORKING SPACE PROVIDED NEW PANEL IN ELECTRICAL ROOM
OPEN 07/18/2016 07/18/2016
 
004 (999) OTHER
(CELLAR)GREEN CONDUCTORS USED AS UNGROUNDED CONDUCTORS FOR ELECTRIC ROOM ANDMOTOR CIRCUIT OUTSIDE
RSLV 07/18/2016 07/18/2016 11/03/2016
 
005 (999) OTHER
(CELLAR) 4/0 CONDUCTOR NOT FUSED PROPERLY
RSLV 07/18/2016 07/18/2016 11/03/2016
 
006 (999) OTHER
(GROUND FLOOR) NO DIRECTORY PROVIDED ON PANEL
RSLV 07/18/2016 07/18/2016 11/03/2016
 
007 (999) OTHER
(GROUND FLOOR) OUTDOOR SPLICED BOX NOT SEALED
RSLV 07/18/2016 07/18/2016 11/03/2016
 
008 (999) OTHER
(GROUND FLOOR) LOW AND 208 VOLT IN SAME JCT BOX NOT PERMITTED
RSLV 07/18/2016 07/18/2016 11/03/2016
 
009 (999) OTHER
(GROUND FLOOR) #10 CONDUCTOR USED AS PARALLEL FOR OUTDOOR MOTOR
RSLV 07/18/2016 07/18/2016 11/03/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Complaint  |  Electrical Inspection Work Order  |  Back