BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B391331
Premises: 376 UNION STREET BROOKLYN BIN: 3007285     Block: 436   Lot: 31
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 376 UNION ST Census Tract:   75 Health Area:  2500
1ST 2ND 3RD 4TH FL Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
Special Place Name:   SMITH ST
Related Job Number:    321002696
DOB Cross Street(s):   SMITH STREET,    HOYT STREET
Status:   C - JOB IS SIGNED OFF 04/27/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/25/2015 9:28 PM
Application Entered:   01/25/2015 Job Start Date:   01/29/2015
Last Change:   04/27/2016 Job End Date:   05/19/2015
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     03/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010880 Licensee Name: ANTHONY ILLIANO
Firm: 002159 Firm Name: ALECTRA INC
Firm Phone: 718-522-3893  Firm Address: 125 DIKEMAN STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $177.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TAL GOLUMB
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  4/3. 6/3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  25  15  15  25         
002  13         
003  12  17  10  12         
004    16  14  11  16         
Buildings Total 60  59  43  58              
Total Units : 228 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/26/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B391331
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/03/2016 02/03/2016 DIT N (8) (0) Y
INSPECTION COMMENTS: CALL CONTRACTOR APPOINTMENT WAS CANCEL.
 
(2) 02/24/2016 02/26/2016 DAH V (50) (1)
INSPECTION COMMENTS: NEUTRAL IS BONDED IN PANEL ON THE 2ND. FLOOR
 
(3) 03/29/2016 03/30/2016 HRB C R (60) (0)
INSPECTION COMMENTS: PASSED

OBJECTION FOR APPLICATION #: B391331
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 003)NEUTRAL IS BONDED AFTER SVC IN PANEL ARTICLE 250.24(A)(5)
RSLV 02/24/2016 02/24/2016 03/29/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.