BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B391250
Premises: 296 FLATBUSH AVENUE EXTENSION BROOKLYN BIN: 3398355     Block: 149   Lot: 101
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 336 FLATBUSH AV EXTENSION Census Tract:   15
SC,C,GND,2-35,ROOF,BULKHD 1&2 Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Special Place Name:   CITY POINT TOWER 2
Related Job Number:    320515723
DOB Cross Street(s):   WILLOUGHBY STREET,    FLEET STREET
Status:   C - JOB IS SIGNED OFF 12/08/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/22/2015 Job Start Date:   01/09/2015
Last Change:   12/08/2017 Job End Date:   01/09/2018
Appointment Status:   
Last Inspection By:   JEROME BLACK       On     12/07/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012292 Licensee Name: ANTHONY FIGUCCIO
Firm: 002661 Firm Name: S. J. ELECTRIC INC.
Firm Phone: 718-643-7274  Firm Address: 94-02 LINDEN BLVD OZONE PARK NY 11417 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320515723
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52780     Submittal #: 15A0117  
Owner / Occup: ALOK JAINE
Owner Business Name: LEND LEASE CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  2-400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1-4000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  327  #2
B. Over #2 to 1/0  139  #8,#6,#4,#3,#2
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  152  500MCM 750MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  440  100A
C. 3 Phase Up to 225 AMPS  40  100A, 125A, 225A
D. 3 Phase Over 225 AMPS  16  4000A 800A 600A 400&250A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SC1    12    16  154      45 
CEL                 
GND    14            30 
001  BH1  10    28         
002                 
002  BH2  10    371         
003                 
004                 
005                 
006    88    21  20  59      11  58 
007    178  360    40  178             
008    178  360    40  178             
009    178  360    40  178             
010    178  360    40  178             
011    178  360    40  178             
012    178  360    40  178             
013    178  360    40  178             
014    178  360    40  178             
015    178  310    36  178             
016    178  310    36  178             
017    178  310    36  178             
018    178  310    36  178             
019    178  310    36  178             
020    178  310    36  178             
021    178  310    36  178             
022    178  310    36  178             
023    178  310    36  178             
024    178  310    36  178             
025    178  310    36  178             
026    155  245    35  155             
027    155  245    35  155             
028    155  245    35  155             
029    155  245    35  155             
030    155  245    35  155             
031    155  245    35  155             
032    155  245    35  155             
033    155  245    35  155             
034    155  245    35  155             
035    155  245    35  155             
ROF    12  10    12  10  350      1135 
Buildings Total 4978  8924    1142  4978     962          1268 
Total Units : 22252 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 440 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 441 - Removed Meters 0 = Total Meters 441

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/22/2015 Notice: 1 - FIRST NOTICE 04/06/2017
Power Issued: 01/22/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B391250
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/04/2017 04/06/2017 CLC V (450) (12)
INSPECTION COMMENTS: INSPECTION FAIL NEED ACCESS TO AT LEASE 40% OF THE APARTMENTS NOT A FINAL INSPECTION
 
(2) 07/31/2017 07/31/2017 DIT J Y (120) (0)
INSPECTION COMMENTS: OBJECTION REMAINS(OVER CURRENT PROTECTION NOT PROVIDED FOR TRANSFORMER SECONDARY SIDE OBJ #001)
 
(3) 12/07/2017 12/08/2017 JKJ C R (45) (0)
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: B391250
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001)1FL PANEL ON THE SECONDARY SIDE MORE THAN SIX DISCONNECT AREPROVIDED 450.3 B NOTES 2
RSLV 04/04/2017 04/04/2017 12/07/2017
 
002 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
(FLOOR: 006) BALCONY CONDUIT FEEDING LIGHTS NOT SUPPORTED
RSLV 04/04/2017 04/04/2017 07/31/2017
 
003 (999) OTHER
(FLOOR: 006) BALCONY GFCI NOT WR 406.8 A
RSLV 04/04/2017 04/04/2017 07/31/2017
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 038) APT 38 B PANEL MISSING KO
RSLV 04/04/2017 04/04/2017 07/31/2017
 
005 (999) OTHER
(FLOOR: 038) APT 38 B PANEL MULTI WIRE CIRCUITS IN USE 210.4 B
RSLV 04/04/2017 04/04/2017 07/31/2017
 
006 (999) OTHER
(FLOOR: 046) ATS ROOM TRANSFORMERS NOT PROPERLY GROUNDED 250.30 A
RSLV 04/04/2017 04/04/2017 07/31/2017
 
007 (999) OTHER
(FLOOR: 046)LOW LEVEL ELECTRICAL ROOM PRIMARY SIDE 800AMP 3FT WORK SPACE INFRONT NOT PROVIDED 110.26 A
RSLV 04/04/2017 04/04/2017 12/07/2017
 
008 (999) OTHER
(ALL FLOORS)ALL PANELS MULTI WIRES AREN'T SIMULTANEOUSLY DISCONNECT 210.4 B
RSLV 04/04/2017 04/04/2017 07/31/2017
 
009 (999) OTHER
(BASEMENT) FIRE ALARM SERVICE DISCONNECT HAS NO NEUTRAL 250.24 C
RSLV 04/04/2017 04/04/2017 07/31/2017
 
010 (999) OTHER
(BASEMENT) 30 AMP SERVICE DISCONNECT NEUTRAL NOT NO BAR 250.24 C
RSLV 04/04/2017 04/04/2017 07/31/2017
 
011 (999) OTHER
(ROOF) GENERATOR NEUTRAL NOT BONDED 250.20 D
RSLV 04/04/2017 04/04/2017 07/31/2017
 
012 (999) OTHER
(ROOF) GROUNDING ELECTRODE NOT PROVIDED TO THE GENERATOR 250.30 A 3
RSLV 04/04/2017 04/04/2017 07/31/2017