| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
2-400A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
1 |
1-4000A |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
327 |
#2 |
| B. Over #2 to 1/0 |
139 |
#8,#6,#4,#3,#2 |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
152 |
500MCM 750MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
440 |
100A |
| C. 3 Phase Up to 225 AMPS |
40 |
100A, 125A, 225A |
| D. 3 Phase Over 225 AMPS |
16 |
4000A 800A 600A 400&250A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 001)1FL PANEL ON THE SECONDARY SIDE MORE THAN SIX DISCONNECT AREPROVIDED 450.3 B NOTES 2 |
RSLV |
04/04/2017 |
04/04/2017 |
12/07/2017 |
| |
| 002 |
( 8) |
CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC) (FLOOR: 006) BALCONY CONDUIT FEEDING LIGHTS NOT SUPPORTED |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 003 |
(999) |
OTHER (FLOOR: 006) BALCONY GFCI NOT WR 406.8 A |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 004 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 038) APT 38 B PANEL MISSING KO |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 005 |
(999) |
OTHER (FLOOR: 038) APT 38 B PANEL MULTI WIRE CIRCUITS IN USE 210.4 B |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 006 |
(999) |
OTHER (FLOOR: 046) ATS ROOM TRANSFORMERS NOT PROPERLY GROUNDED 250.30 A |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 007 |
(999) |
OTHER (FLOOR: 046)LOW LEVEL ELECTRICAL ROOM PRIMARY SIDE 800AMP 3FT WORK SPACE INFRONT NOT PROVIDED 110.26 A |
RSLV |
04/04/2017 |
04/04/2017 |
12/07/2017 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS)ALL PANELS MULTI WIRES AREN'T SIMULTANEOUSLY DISCONNECT 210.4 B |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 009 |
(999) |
OTHER (BASEMENT) FIRE ALARM SERVICE DISCONNECT HAS NO NEUTRAL 250.24 C |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 010 |
(999) |
OTHER (BASEMENT) 30 AMP SERVICE DISCONNECT NEUTRAL NOT NO BAR 250.24 C |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 011 |
(999) |
OTHER (ROOF) GENERATOR NEUTRAL NOT BONDED 250.20 D |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |
| |
| 012 |
(999) |
OTHER (ROOF) GROUNDING ELECTRODE NOT PROVIDED TO THE GENERATOR 250.30 A 3 |
RSLV |
04/04/2017 |
04/04/2017 |
07/31/2017 |