BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B390825
Premises: 329 LINCOLN PLACE BROOKLYN BIN: 3029532     Block: 1176   Lot: 68
   
Application Completed and Certified

Filed: 329 LINCOLN PL Census Tract:   215 Health Area:  2720
APT. 3L Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
DOB Cross Street(s):   UNDERHILL AVENUE,    WASHINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 08/19/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/13/2015 11:31 AM
Application Entered:   01/13/2015 Job Start Date:   01/13/2015
Last Change:   08/19/2015 Job End Date:   01/13/2016
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     08/12/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011372 Licensee Name: STEVEN DENNISON
Firm: 003326 Firm Name: DENNISON ELECTRIC CORP
Firm Phone: 718-803-6421  Firm Address: 37-31 58TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $54.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BENNAT BERGER
Owner Business Name: 315-329 LINCOLN PLACE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3L    35  10  20             
Buildings Total   35  10  20                
Total Units : 69 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/19/2015 Notice: 1 - FIRST NOTICE 02/19/2015
Power Issued: 08/19/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING LIGHTS, SWITCHES, OUTLETS, A/C'S.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B390825
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/10/2015 02/19/2015 CCH A (50) (5) Y
INSPECTION COMMENTS: N
 
(2) 03/03/2015 03/09/2015 CLC N (60) (0) Y
INSPECTION COMMENTS: CONTR NO SHOW, NO ACCESS
 
(3) 08/12/2015 08/19/2015 DAH C R E (15) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B390825
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
DEF WIRING BRAKER TRIPPING
RSLV 02/10/2015 02/10/2015 08/12/2015
 
002 (999) OTHER
A DRYER OUTLET BOX NOT BONDED MC CABLE 250.146
RSLV 02/10/2015 02/10/2015 08/12/2015
 
003 (999) OTHER
B NO GFCI LEFT SIDE SINK KITCHEN 210.52 C.1
RSLV 02/10/2015 02/10/2015 08/12/2015
 
004 (999) OTHER
C OUTLET NOT ADJACENT TO SINK BATHROOM 210.52D
RSLV 02/10/2015 02/10/2015 08/12/2015
 
005 (999) OTHER
D ALL BATHROOMS LIGHTS OUTLETS SAME CIRCUIT 210.11 C3X
RSLV 02/10/2015 02/10/2015 08/12/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.