| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
1 SET 500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(138) |
METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY (GROUND FLOOR) RACEWAY TO WATER MAIN NOT CONTINUOUS |
RSLV |
03/22/2016 |
03/22/2016 |
05/25/2016 |
| |
| 002 |
(185) |
MULTIPLE SOURCE DISCONNECTS NOT GROUPED/IDENTIFIED (GROUND FLOOR) 12/3 CIRCUITS NOT ID IN BOTH SERVICE SWITCHES |
RSLV |
03/22/2016 |
03/22/2016 |
05/25/2016 |
| |
| 003 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH (GROUND FLOOR) IN MAIN SERVICE SWITCH |
RSLV |
03/22/2016 |
03/22/2016 |
05/25/2016 |
| |
| 004 |
(228) |
USING PANEL AS A RACEWAY (GROUND FLOOR) MAIN SERVICE SWITCH TO SUB PANEL |
RSLV |
03/22/2016 |
03/22/2016 |
05/25/2016 |
| |
| 005 |
(247) |
SIMULTANEOUS OPENING OF POLES (GROUND FLOOR)12/3 CIRCUITS NOT ON A 2 POLE BREAKER IN BOTH SERVICE SWITCHES |
RSLV |
03/22/2016 |
03/22/2016 |
05/25/2016 |
| |
| 006 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (GROUND FLOOR) IN HOUSE SERVICE SWITCHS |
RSLV |
03/22/2016 |
03/22/2016 |
05/25/2016 |
| |
| 007 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (GROUND FLOOR) BOTH SERVICE SWITCHES |
RSLV |
03/22/2016 |
03/22/2016 |
05/25/2016 |