Premises: 3096 BRIGHTON 7 STREET BROOKLYN BIN: 3245120     Block: 8691   Lot: 57
   
Application Completed and Certified

Filed: 3100 BRIGHTON 7 ST Census Tract:   360.02 Health Area:  9110
ALL Admin Area:   B - BROOKLYN Inspection Area:   R
BROOKLYN, NY 11235 Community Board:   313
DOB Cross Street(s):   BRIGHTON BEACH AVENUE,    BRIGHTWATER COURT
Status:   C - JOB IS SIGNED OFF 04/28/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/07/2014 3:56 PM
Application Entered:   11/07/2014 Job Start Date:   11/07/2014
Last Change:   04/28/2015 Job End Date:   06/15/2015
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     03/20/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012465 Licensee Name: MOSHE ROTH
Firm: 004272 Firm Name: B.P. ELECTRIC CORP
Firm Phone: 718-853-4949  Firm Address: 1425 37TH STREET BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $2,572.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: A KLIEN
Owner Business Name: EMOR SK LIMITED PARTNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  2  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  59  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  60  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      20                   
002      20                   
003      20                   
004      20                   
005      20                   
006      20                   
Buildings Total   120                      
Total Units : 120 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 59 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/07/2014 Notice: 1 - FIRST NOTICE 03/17/2015
Power Issued: 11/07/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B388463
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/02/2015 02/10/2015 EBA A E (120) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 03/13/2015 03/17/2015 JTE A R D (70) (5) Y
INSPECTION COMMENTS: NONE
 
(3) 03/20/2015 03/24/2015 CJE C R E (35) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B388463
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERVICE EQUIPMENTNOT BONDED TOGETHER, LINE SIDE ON THROFT
RSLV 02/02/2015 02/02/2015 03/13/2015
 
002 (999) OTHER
MORETHAN 8 WIRES IN PIPES AT METERBANK, DERATING CHAPT 9 TAB 1
RSLV 02/02/2015 02/02/2015 03/13/2015
 
003 (999) OTHER
RISERS NOT SEALED AT SMOOTH
RSLV 02/02/2015 02/02/2015 03/13/2015
 
004 (999) OTHER
WHITE LINE USED AS GROUNDING CONDUCTOR IN PLP 200.6.A
RSLV 02/02/2015 02/02/2015 03/13/2015
 
005 (999) OTHER
WHERE MULTIPLE SETS OF S.E.C ARE USED 2-SETS OF 4-WIRE 500MCM THE GE.C SHALL NOT BE LESS THAN THE REQUIRE ON 250.66/250.30
RSLV 03/13/2015 03/13/2015 03/20/2015
 
006 (999) OTHER
THE E.G.C BONDING LINE SIDE TROUGH SHALL COMPLY WITH ART 250.12
RSLV 03/13/2015 03/13/2015 03/20/2015
 
007 (999) OTHER
ALL EMT CARRYING APT FEEDERS NOT PROPERLY SUPPORTED THROUGHOUT 258.30
RSLV 03/13/2015 03/13/2015 03/20/2015
 
008 (999) OTHER
ALL JUNCTION BOXES FOR APT FEEDERS NOT PROPERLY SUPPORTED 314.23
RSLV 03/13/2015 03/13/2015 03/20/2015
 
009 (999) OTHER
APT FEEDERS TRAVELING THROUGH BLDG RAFT NOT SUPPORTED ACCORDING TO 348.30
RSLV 03/13/2015 03/13/2015 03/20/2015