| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
|
| C. 201 Up to 600 AMPS |
2 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
59 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
6 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
60 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER SERVICE EQUIPMENTNOT BONDED TOGETHER, LINE SIDE ON THROFT |
RSLV |
02/02/2015 |
02/02/2015 |
03/13/2015 |
| |
| 002 |
(999) |
OTHER MORETHAN 8 WIRES IN PIPES AT METERBANK, DERATING CHAPT 9 TAB 1 |
RSLV |
02/02/2015 |
02/02/2015 |
03/13/2015 |
| |
| 003 |
(999) |
OTHER RISERS NOT SEALED AT SMOOTH |
RSLV |
02/02/2015 |
02/02/2015 |
03/13/2015 |
| |
| 004 |
(999) |
OTHER WHITE LINE USED AS GROUNDING CONDUCTOR IN PLP 200.6.A |
RSLV |
02/02/2015 |
02/02/2015 |
03/13/2015 |
| |
| 005 |
(999) |
OTHER WHERE MULTIPLE SETS OF S.E.C ARE USED 2-SETS OF 4-WIRE 500MCM THE GE.C SHALL NOT BE LESS THAN THE REQUIRE ON 250.66/250.30 |
RSLV |
03/13/2015 |
03/13/2015 |
03/20/2015 |
| |
| 006 |
(999) |
OTHER THE E.G.C BONDING LINE SIDE TROUGH SHALL COMPLY WITH ART 250.12 |
RSLV |
03/13/2015 |
03/13/2015 |
03/20/2015 |
| |
| 007 |
(999) |
OTHER ALL EMT CARRYING APT FEEDERS NOT PROPERLY SUPPORTED THROUGHOUT 258.30 |
RSLV |
03/13/2015 |
03/13/2015 |
03/20/2015 |
| |
| 008 |
(999) |
OTHER ALL JUNCTION BOXES FOR APT FEEDERS NOT PROPERLY SUPPORTED 314.23 |
RSLV |
03/13/2015 |
03/13/2015 |
03/20/2015 |
| |
| 009 |
(999) |
OTHER APT FEEDERS TRAVELING THROUGH BLDG RAFT NOT SUPPORTED ACCORDING TO 348.30 |
RSLV |
03/13/2015 |
03/13/2015 |
03/20/2015 |