Electrical Application Details for App #: B387918
Premises: 79 BRIDGE STREET BROOKLYN BIN: 3000141     Block: 55   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 79 BRIDGE ST Census Tract:   21 Health Area:  1000
1ST FL. Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   FRONT STREET,    YORK STREET
Status:   C - JOB IS SIGNED OFF 11/18/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/28/2014 10:42 AM
Application Entered:   10/28/2014 Job Start Date:   10/28/2014
Last Change:   11/18/2016 Job End Date:   10/28/2016
Appointment Status:   
Last Inspection By:   SEVERIANO JOHN       On     11/16/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011212 Licensee Name: PAUL LEFKOWITZ
Firm: 001756 Firm Name: BLZ ELECTRIC INC.
Firm Phone: 718-677-5900  Firm Address: 1243 EAST 15TH STREET BROOKLYN NY 11230 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $499.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FRANK CARONE
Owner Business Name: CHC SURGICAL CENTER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  42CKTS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      100    20  110  15  60 
Buildings Total   100    20  110     15        60 
Total Units : 309 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/28/2014 Notice: 1 - FIRST NOTICE 11/15/2016
Power Issued: 10/28/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B387918
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/23/2016 10/12/2016 CJE V (88) (4)
INSPECTION COMMENTS: CORRECT ALL OBJECTIONS.
 
(2) 11/10/2016 11/15/2016 CJH V R (56) (1)
INSPECTION COMMENTS: FAIL
 
(3) 11/16/2016 11/16/2016 SVJ C R (6) (0)
INSPECTION COMMENTS: OK AS PER JOSEPH ZEC,, ADVISORY MEMBER

OBJECTION FOR APPLICATION #: B387918
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (216) LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE
(GROUND FLOOR)SHIELDED CABLE FOR DIMMERS IN SAME ENCLOSURE FOR POWER IN FIXTURES.ART. 725.
RSLV 09/23/2016 09/23/2016 11/10/2016
 
002 (220) DOUBLE LUGGING IN SERVICE SWITCH
(GROUND FLOOR)DOUBLE LUGGING OF G.E.C ON EMERGENCY SIZE OF ASCO SWITCH.
RSLV 09/23/2016 09/23/2016 11/10/2016
 
003 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(GROUND FLOOR) QUICK DISCONNECTS NOT PROVIDED. ART. 410.130(G1)
RSLV 09/23/2016 09/23/2016 11/10/2016
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(GROUND FLOOR)COMMON GROUNDING CONNECTION NOT PROPERLY INSTALLED. ART. 250.66(F3)
RSLV 09/23/2016 09/23/2016 11/10/2016
 
005 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(GROUND FLOOR) GND FL RECEPT OUTLETS NOT GROUNDED PROPERLY 250.146
RSLV 11/10/2016 11/10/2016 11/16/2016