| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
2 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
22 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
22 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
1 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER CELLAR SVC AREA COMMUNICATION BAR NOT INSTALLED 250.94 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 002 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED PLP GND CONDUCTOR NOT TERMINATED 250.112 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 003 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER CELLAR SVC WATER METER JUMPER 250.53 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 004 |
(222) |
USING NON METALLIC SEALTITE NOT APPROVED CELLAR BOOSTER PUMP CONTROLLER 356.10 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 005 |
(999) |
OTHER CELLAR BOILER ROOM PNL CIRCUIT NOT GROUPED 210.4D |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 006 |
(999) |
OTHER CELLAR BOILER ROOM PNL MULTI CIRCUIT NOT SIMUTANEOUSLY 210.4B |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 007 |
(999) |
OTHER CELLAR SVC SWITCH DIS SWITCHES PLAZUE NOT PROVIDED 230.2E |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 008 |
(999) |
OTHER REAR SUPER APT KITCHEN COUNTER TOP GFCI HOOD SHARE CIRCUIT 210.52 B2 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 009 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION ALL FL THROUGHOUT BATHROOM LUMINARES 410.10 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 010 |
(999) |
OTHER APT 4.5.6.9 KITCHEN COUNTER GFCI SHARE WITH LIGHTS CIRCUITS 210.52B2 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 011 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED ALL FL THROUGHOUT RECEPTICLES OUTLETS 250.146 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 012 |
(999) |
OTHER APT 1,7,11,15 KITCHEN COUNTER TOP RECEPTICLES OUTLETS NOT LOCATED PROPERLY 210.52 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 013 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE APT 5 BATHROOM GFCI OUTLET 110.2 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |
| |
| 014 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX APT 28 SUPER APT KO MISSING 110.12 |
RSLV |
04/02/2015 |
04/02/2015 |
04/21/2015 |