BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B387738
Premises: 1924 54 STREET BROOKLYN BIN: 3130980     Block: 5495   Lot: 43
   
Application Completed and Certified

Filed: 1924 54 ST Census Tract:   468 Health Area:  8110
BASEMENT / 001/ 002 Admin Area:   B - BROOKLYN Inspection Area:   N
BROOKLYN, NY 11204 Community Board:   312
DOB Cross Street(s):    19 AVENUE,    20 AVENUE
Status:   C - JOB IS SIGNED OFF 02/10/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/23/2014 10:33 AM
Application Entered:   10/23/2014 Job Start Date:   10/23/2014
Last Change:   02/10/2015 Job End Date:   10/23/2014
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     01/22/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011988 Licensee Name: ZVI SARAFRAZ
Firm: 003730 Firm Name: HORSEPOWER ELECTRIC.&
Firm Phone: 718-437-6937  Firm Address: 4101 1ST AVENUE MAINTENANCE, CORP BROOKLYN NY 11232 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $61.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ISRAEL LONDINSKY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001    11  13    11             
002    10  12    10             
Buildings Total 25  30    16  25                
Total Units : 96 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/31/2015 Notice: 1 - FIRST NOTICE 11/25/2014
Power Issued: 01/31/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B387738
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/20/2014 11/25/2014 JTE V (40) (10) Y
INSPECTION COMMENTS: MUST INSPECT ALL BRANCH CKTS AFTER AFCI IS PROVIDED/MUST ADD SERVICE WORK APP, NOT A FINAL
 
(2) 01/12/2015 01/20/2015 DAH N (45) (0) Y
INSPECTION COMMENTS: N
 
(3) 01/22/2015 01/31/2015 DAH C R E (50) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B387738
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
SET OF 3W 3/0 S.E.C RAN THROUGH 1 1/4 CONDUIT (A. TABLE C8)
RSLV 11/20/2014 11/20/2014 01/22/2015
 
002 (999) OTHER
NO COMMUNICATION BAR 250.94
RSLV 11/20/2014 11/20/2014 01/22/2015
 
003 (999) OTHER
MIGB NOT BONDED TO ENCLOSURE PANEL 250.92B4
RSLV 11/20/2014 11/20/2014 01/22/2015
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
MAIN G.E.C NOT TO SERVICE NEUTRAL BAR
RSLV 11/20/2014 11/20/2014 01/22/2015
 
005 (999) OTHER
ALL MULTIWIRE CKT'S NOT ON COMMON TRIP 210.4B
RSLV 11/20/2014 11/20/2014 01/22/2015
 
006 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
FIXTURES MISSING COVER LENS
RSLV 11/20/2014 11/20/2014 01/22/2015
 
007 (999) OTHER
NO DISC/SW PROVIDED OUTSIDED BOILER ROOM 424.19
RSLV 11/20/2014 11/20/2014 01/22/2015
 
008 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
EXTENSION CORD PLUGS USE AS PERMANENT OUTLETS FOR KITCHEN COUNTER UNDER CABINETS
RSLV 11/20/2014 11/20/2014 01/22/2015
 
009 (999) OTHER
NO GFCI FRONT OF HOUSE PROVIDED 210.52E1
RSLV 11/20/2014 11/20/2014 01/22/2015
 
010 (999) OTHER
REAR DECK GFCI NOT WR/TR LISTED 406.8
RSLV 11/20/2014 11/20/2014 01/22/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order