BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B386873
Premises: 4301 7 AVENUE BROOKLYN BIN: 3011002     Block: 732   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 4305 7 AV Census Tract:   92 Health Area:  6600
GROUND FLOOR Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11232 Community Board:   307
Special Place Name:   PS K169- BROOKLYN
DOB Cross Street(s):    43 STREET,    44 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/02/2014 2:39 PM
Application Entered:   10/02/2014 Job Start Date:   10/02/2014
Last Change:   08/22/2025 Job End Date:   10/02/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     12/11/2014      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 011028 Licensee Name: WILLIAM NIEVES
Firm: 002945 Firm Name: CHARAN ELEC'L ENTERP'S IN
Firm Phone: 718-706-9612  Firm Address: 9-11 40TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $135.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HECTOR ORTIZ
Owner Business Name: DEPARTMENT OF EDUCATION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/15/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALL A NEW PANEL IN KITCHEN AND AN OUTLET FOR STEAM TABLE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B386873
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/11/2014 12/15/2014 DAH A (30) (3) Y
INSPECTION COMMENTS: EXISTING #200 SVC

OBJECTION FOR APPLICATION #: B386873
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
SVC SW TAP OF 3/0 IS MARK IN EXISTING 2000A CT CABINET
OPEN 12/11/2014 12/11/2014
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
200A SVC SW NEUTRAL NOT BONDED
OPEN 12/11/2014 12/11/2014
 
003 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
NEW 200A SVC SW TAPPED OFF 2800A SVC
OPEN 12/11/2014 12/11/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.