BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B386552
Premises: 109 SOUTH 5 STREET BROOKLYN BIN: 3063433     Block: 2443   Lot: 34
   
Application Completed and Certified

Filed: 109 S 5 ST Census Tract:   549 Health Area:  0500
UNIT 103 Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11249 Community Board:   301
DOB Cross Street(s):   BERRY STREET,    BEDFORD AVENUE
Status:   C - JOB IS SIGNED OFF 01/22/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/24/2014 6:56 PM
Application Entered:   09/24/2014 Job Start Date:   09/24/2014
Last Change:   01/22/2015 Job End Date:   09/24/2015
Appointment Status:   
Last Inspection By:   BANYA, E       On     01/16/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010730 Licensee Name: ALBERT MARGOLIN
Firm: 003031 Firm Name: GSA ELECTRIC CORP.
Firm Phone: 718-922-3300  Firm Address: 9302 DITMAS AVENUE BROOKLYN NY 11236 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
012290 MARGOLIN, GREGG 003031 GSA ELECTRIC CORP. RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $186.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   COFFEE SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: BENE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP SWITCH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4 # 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 A 3 PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  103  27  38    27             
Buildings Total 27  38    27                
Total Units : 95 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/08/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B386552
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/30/2014 01/07/2015 HRB V (45) (5) Y
INSPECTION COMMENTS: NOT FINAL/NEED TO RECHECK WHOLE JOB
 
(2) 12/30/2014 01/08/2015 HRB V R (45) (5) Y
INSPECTION COMMENTS: NOT FINAL NEED TO RECHECK WHOLE JOB
 
(3) 01/16/2015 01/22/2015 EBA C R (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B386552
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
THRU-OUT: QUICK DISCONNECT
RSLV 12/30/2014 12/30/2014 12/30/2014
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
KITCHEN: GFI IN FOOD PREP AREA
RSLV 12/30/2014 12/30/2014 12/30/2014
 
003 (999) OTHER
KITCHEN: NO FUSE COORDINATION FOR LINK FUSE(110.2.B5)
RSLV 12/30/2014 12/30/2014 12/30/2014
 
004 (999) OTHER
KITCHEN: DRILLED AND TAP THE C OF O DETAIL(110.2.B5)
RSLV 12/30/2014 12/30/2014 12/30/2014
 
005 (999) OTHER
KITCHEN: NEED LOAD CALTIONS FOR NEW WAVE 110.2.B5)
RSLV 12/30/2014 12/30/2014 12/30/2014
 
006 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
THRU-OUT: QUICK DISCONNECT
RSLV 12/30/2014 12/30/2014 01/16/2015
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
KITCHEN: GFI IN FOOD PREP AREA
RSLV 12/30/2014 12/30/2014 01/16/2015
 
008 (999) OTHER
KITCHEN: NEED LOAD CALCULATION FOR NEW WIRE.110.2 (B5)
RSLV 12/30/2014 12/30/2014 01/16/2015
 
009 (999) OTHER
KITCHEN: NO FUSE COORDINATION FOR LINK FUSE 110.2(B5)
RSLV 12/30/2014 12/30/2014 01/16/2015
 
010 (999) OTHER
DRILL AND TAP THE COPO DETAIL 110.2(B5)
RSLV 12/30/2014 12/30/2014 01/16/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order