| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
1 |
3/0 |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER SUPPLIMENTAL GROUND NOT PROVIDED ARTICLE 210 |
RSLV |
04/30/2015 |
05/21/2015 |
06/17/2015 |
| |
| 002 |
(999) |
OTHER GND FL JUMPER NOT PROVIDED AT WTR MTR ARTICLE 250.53 (D) |
RSLV |
04/30/2015 |
05/21/2015 |
06/17/2015 |
| |
| 003 |
(999) |
OTHER DEVICES SET BACK MORE THAN 1/4 ARTICLE 314.20 |
RSLV |
04/30/2015 |
04/30/2015 |
05/21/2015 |
| |
| 004 |
(999) |
OTHER RECEPTICLES INSTALLED BEHIND COUNTER# SURFACE ARTICLE 406.4 (E) |
RSLV |
04/30/2015 |
04/30/2015 |
05/21/2015 |
| |
| 005 |
(999) |
OTHER RECEPTICLES INSTALLED FACING UP ARTICLE 406.4 (E) |
RSLV |
04/30/2015 |
04/30/2015 |
05/21/2015 |
| |
| 006 |
(999) |
OTHER DS NOT PROVIDED AT HVAC UNIT ARTICLE 30.74 |
RSLV |
04/30/2015 |
04/30/2015 |
05/21/2015 |
| |
| 007 |
(999) |
OTHER NOT APPLIED TO RACEWAY ABOVE |
RSLV |
04/30/2015 |
04/30/2015 |
05/21/2015 |
| |
| 008 |
(999) |
OTHER SVC PNL MORE THAN 3 CONDUCTORS TABLE 310. TABLE C1 |
RSLV |
04/30/2015 |
04/30/2015 |
05/21/2015 |
| |
| 009 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ECG IN DS FOR HVAC IS NOT BONDED IN SWITCH |
RSLV |
04/30/2015 |
04/30/2015 |
05/21/2015 |
| |
| 010 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED 2ND FL-OVEN IN KITCHEN NO DISSCONNECT WITH INSIGHT |
RSLV |
05/21/2015 |
05/21/2015 |
06/17/2015 |