BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B384711
Premises: 393 LEFFERTS AVENUE BROOKLYN BIN: 3397193     Block: 1321   Lot: 40
   
Application Completed and Certified

Filed: 393 LEFFERTS AV Census Tract:   329 Health Area:  4800
BASEMENT /ROOF Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11225 Community Board:   309
Related Job Number:    301540170
DOB Cross Street(s):   NOSTRAND AVENUE,    NEW YORK AVENUE
Status:   C - JOB IS SIGNED OFF 10/14/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/13/2014 11:04 AM
Application Entered:   08/13/2014 Job Start Date:   08/13/2014
Last Change:   10/14/2015 Job End Date:   04/13/2015
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     10/06/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011781 Licensee Name: THEODORE THEODOROPOULOS
Firm: 002302 Firm Name: T & T ELECTRICAL CORP.
Firm Phone: 718-721-3300  Firm Address: 24-30 47TH STREET ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $551.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRISTOS THOMOPOULOS
Owner Business Name: SEABREEZE GEN CONT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    12  12  12  27  20         
001  17  65  15  25  19         
002  27  165  21  49  47             
003  27  165  21  49  47             
004  27  165  21  49  47             
005  27  165  21  49  47             
006  27  165  21  49  47             
007  22  122  17  41  39             
ROF    12         
Buildings Total 193  1029  133  315  334     51           
Total Units : 2055 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/13/2015 Notice: 1 - FIRST NOTICE 09/11/2015
Power Issued: 10/13/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B384711
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/31/2015 09/11/2015 DAH A (60) (3) Y
INSPECTION COMMENTS: N
 
(2) 10/06/2015 10/13/2015 CJH C R E (65) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B384711
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
LUMINARIES ARE NOT APPROVED FOR WET ZONE 404.4
RSLV 08/31/2015 08/31/2015 10/06/2015
 
002 (999) OTHER
F.P PNL IS BEING USES AS LAP BOX JOCKEY PUMP DS ARTICLE 695 (6) (F)
RSLV 08/31/2015 08/31/2015 10/06/2015
 
003 (999) OTHER
DS FROM STEP UP TRANSFORMER NOT LABELED ARTICLE 404. 110.26
RSLV 08/31/2015 08/31/2015 10/06/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back