| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
2 |
100 AMPS 220 VOLTS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER POOR WORKMANSHIP, AFCI, REGULAR BREAKERS ALL MIXED UP IN PANELS (110.12) |
RSLV |
12/09/2014 |
12/09/2014 |
01/07/2015 |
| |
| 002 |
(999) |
OTHER MULTI CIRCUITS NOT SIMULTANEOUSLY DISCONNECTED (210.4)(B) |
RSLV |
12/09/2014 |
01/07/2015 |
02/10/2015 |
| |
| 003 |
(999) |
OTHER BATHROOM LIGHTS NOT VAPOR PROOF (410.10)(A) |
RSLV |
12/09/2014 |
01/07/2015 |
02/10/2015 |
| |
| 004 |
(999) |
OTHER 4R INSUFFICIENT KITCHEN COUNTER RECEPTICLE OUTLETS 210.52 (C4) |
RSLV |
01/07/2015 |
01/07/2015 |
02/10/2015 |
| |
| 005 |
(999) |
OTHER A MICROWAVE OUTLET NOT TAMPER PROOF 406.11 |
RSLV |
02/10/2015 |
02/10/2015 |
08/12/2015 |
| |
| 006 |
(999) |
OTHER B BATHROOMS LIGHTS OUTLETS SAME CIR 210.11C3X |
RSLV |
02/10/2015 |
02/10/2015 |
08/12/2015 |
| |
| 007 |
(999) |
OTHER C DRYER OUTLET BOX NOT BONDED 250.146 |
RSLV |
02/10/2015 |
02/10/2015 |
08/12/2015 |