Electrical Application Details for App #: B383908
Premises: 869 45 STREET BROOKLYN BIN: 3406988     Block: 742   Lot: 48
   
Application Completed and Certified

Filed: 867 45 ST Census Tract:   94 Health Area:  6600
CELLAR,1,2,3,4/FL, PEN, ROOF Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11220 Community Board:   312
Related Job Number:    320775880
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   C - JOB IS SIGNED OFF 10/08/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/25/2014 4:12 PM
Application Entered:   07/25/2014 Job Start Date:   07/25/2014
Last Change:   10/08/2015 Job End Date:   01/30/2015
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     09/30/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $582.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320775880
Building Used As:   Z - Commercial/Residential (2  Stores, 6 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KE A CHEN
Owner Business Name: CHEN 867 REALTY LLC
Authorized Representative:  KE CHEN
Relationship To Owner:   SELF


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  7  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    12  25    12             
001  1F             
001  1R  12             
002    14  24  16  14             
003  3F  15             
003  3R  13             
004  4F  16             
004  4R  13             
PEN               
ROF                 
Buildings Total 71  134  15  70  71                
Total Units : 361 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 9 - Removed Meters 0 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/25/2014 Notice: 1 - FIRST NOTICE 09/14/2015
Power Issued: 07/25/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B383908
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/21/2015 08/25/2015 CJH V E (65) (5) Y
INSPECTION COMMENTS: AC NOT INSTALLED
 
(2) 09/11/2015 09/14/2015 JTE A R E (30) (1) Y
INSPECTION COMMENTS: AC NOT INSTALLED
 
(3) 09/30/2015 10/06/2015 CJE C R E (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: B383908
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT ELECTRIC ROOM BOX CABLE 320.30
RSLV 08/21/2015 08/21/2015 09/11/2015
 
002 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
BSMT PLP 408.4
RSLV 08/21/2015 08/21/2015 09/11/2015
 
003 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
1ST FL BATHROOM 410.10
RSLV 08/21/2015 08/21/2015 09/11/2015
 
004 (999) OTHER
ALL FLS THROUGHOUT PNL CKT NOT GROUPED 410.10
RSLV 08/21/2015 08/21/2015 09/11/2015
 
005 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
1ST FL 1B PNL 110.14
RSLV 08/21/2015 08/21/2015 09/11/2015
 
006 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
ALL PANELS THROUGHOUT 250.24(A)5
RSLV 09/11/2015 09/11/2015 09/30/2015