Electrical Application Details for App #: B383787
Premises: 94 GREENPOINT AVENUE BROOKLYN BIN: 3398449     Block: 2563   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 94 GREENPOINT AV Census Tract:   565 Health Area:  0100
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11222 Community Board:   301
Related Job Number:    320473750
DOB Cross Street(s):   FRANKLIN STREET,    MANHATTAN AVENUE
Status:   C - JOB IS SIGNED OFF 06/11/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/23/2014 6:50 PM
Application Entered:   07/23/2014 Job Start Date:   07/24/2014
Last Change:   06/11/2016 Job End Date:   07/24/2016
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     05/12/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012208 Licensee Name: JAROSLAW JAROCKI
Firm: 003924 Firm Name: ADA ELECTRIC CORP
Firm Phone: 718-497-5750  Firm Address: 234 CHESTNUT STREET BROOKLYN NY 11208 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $602.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JANUSZ KOWALSKI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  9  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  9  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                   
SWL    12                     
001  1F  28             
001  1R  28             
002  2F  28             
002  2R  28             
003  3F  30             
003  3R  30             
004  4F  12  34    12           
004  4R  12  34    12           
ROF            32         
Buildings Total 94  245    82       40           
Total Units : 461 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 9 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 9 - Removed Meters 0 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/23/2014 Notice: 1 - FIRST NOTICE 04/11/2016
Power Issued: 07/23/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B383787
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/11/2016 04/11/2016 CCH V (85) (2)
INSPECTION COMMENTS: NO TRAVEL TIME
 
(2) 05/12/2016 05/18/2016 HRB C R (25) (0)
INSPECTION COMMENTS: PASSED

OBJECTION FOR APPLICATION #: B383787
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) STOVES+ DRYER BOXES NOT BONDED 250.146
RSLV 04/11/2016 04/11/2016 05/12/2016
 
002 (999) OTHER
(BASEMENT) ROOM NEXT TO SERVICE NOT ON P L P 210.25
RSLV 04/11/2016 04/11/2016 05/12/2016