BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B383456
Premises: 891 4 AVENUE BROOKLYN BIN: 3010176     Block: 685   Lot: 5
   
Application Completed and Certified

Filed: 891 4 AV Census Tract:   84 Health Area:  4400
BSMT,1FL,2FL,3FL Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11232 Community Board:   307
DOB Cross Street(s):    33 STREET,    34 STREET
Status:   C - JOB IS SIGNED OFF 04/09/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/16/2014 7:06 AM
Application Entered:   07/16/2014 Job Start Date:   07/16/2014
Last Change:   04/09/2015 Job End Date:   02/16/2015
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     03/31/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012028 Licensee Name: PATRICK N GILLESPIE
Firm: 003715 Firm Name: WATTS ELECTRICAL CORP
Firm Phone: 718-444-3583  Firm Address: 393 MOTHER GASTON BLVD BROOKLYN NY 11212 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $250.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ISABEL VARGAS
Owner Business Name: NONE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS SWITCH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  SETS #2 WIRE & 6X3 RISER
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  SETS 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1FL  14             
001  1R  14             
002  2FL  14             
002  2R  14             
003  3FL  14             
003  3R  14             
Buildings Total 36  84  12  30  30                
Total Units : 192 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 0 #10-Wire 0
Existing Meters 7 + New Meters 7 - Removed Meters 7 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/16/2014 Notice: 1 - FIRST NOTICE 03/09/2015
Power Issued: 07/16/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B383456
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/19/2015 02/24/2015 CCH V E (55) (6) Y
INSPECTION COMMENTS: NEED ACCESS TO ALL APTS
 
(2) 03/04/2015 03/09/2015 CJH A R E (90) (4) Y
INSPECTION COMMENTS: APT 3L 3R OK
 
(3) 03/17/2015 03/24/2015 DNM N (0) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW OBJECTIONS STILL EXIST
 
(4) 03/31/2015 04/04/2015 CCH C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B383456
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
MIGB NOT BONDED TO FRAME
RSLV 02/19/2015 02/19/2015 03/04/2015
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
THROUGHOUT KO MISSING BASEMENT APT PANELS
RSLV 02/19/2015 02/19/2015 03/04/2015
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
FEEDERS GREENWIRE NOT TO FRAME PANELS SPLICE BOX
RSLV 02/19/2015 02/19/2015 03/04/2015
 
004 (999) OTHER
DERATING FACTOR 18 WIRE IN 2 RACEWAY 310.15
RSLV 02/19/2015 02/19/2015 03/04/2015
 
005 (999) OTHER
EACH APT 60 AMP 230.79
RSLV 02/19/2015 02/19/2015 03/04/2015
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PANEL DIR NOT COMPLETED
RSLV 02/19/2015 02/19/2015 03/04/2015
 
007 (999) OTHER
CELLAR SVC AREA COMMUNICATION BAR NOT INSTALLED 250.94
RSLV 03/04/2015 03/04/2015 03/31/2015
 
008 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
CELLAR PLP GRN CONDUCTOR 250.112
RSLV 03/04/2015 03/04/2015 03/31/2015
 
009 (999) OTHER
1L 2R 3R KITCHEN LUMINARE ON BATHROOM CKT 210.11C3
RSLV 03/04/2015 03/04/2015 03/31/2015
 
010 (999) OTHER
2R MULTI CONDUCTOR NOT SIMUTANEOUSLY 210.4B
RSLV 03/04/2015 03/04/2015 03/31/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order