BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B383310
Premises: 6902 AVENUE U BROOKLYN BIN: 3237617     Block: 8429   Lot: 36
   
Application Completed and Certified

Filed: 6910 AV U Census Tract:   700 Health Area:  8822
GROUND FLOOR Admin Area:   B - BROOKLYN Inspection Area:   Q
BROOKLYN, NY 11234 Community Board:   318
DOB Cross Street(s):   EAST 69 STREET,    EAST 70 STREET
Status:   C - JOB IS SIGNED OFF 11/14/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/11/2014 8:20 PM
Application Entered:   07/11/2014 Job Start Date:   07/11/2014
Last Change:   11/14/2014 Job End Date:   02/20/2015
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     11/12/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009841 Licensee Name: RONALD TWITTY
Firm: 002787 Firm Name: SHALLY ELECTRICAL CO. INC
Firm Phone: 718-782-2020  Firm Address: 611 GRAND STREET BROOKLYN NY 11211 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $0.00
Hurricane Sandy Damage:   Yes
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HELEN PODULSKY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  8  2 SET 4#350 MCM COPPER
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  PLP 60 AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/11/2014 Notice: 1 - FIRST NOTICE 10/20/2014
Power Issued: 07/11/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B383310
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/17/2014 10/20/2014 CJE V G (20) (3) Y
INSPECTION COMMENTS: N
 
(2) 11/12/2014 11/14/2014 CLC C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B383310
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
SER.RM 2 GREEN INSULATED CONDUCTORS USED FOR UNGROUNDED CONDUCTORS ART 250.119
RSLV 10/17/2014 10/17/2014 11/12/2014
 
002 (999) OTHER
SER.RM 2 GREEN INSULATED CONDUCTORS USED AS NEUTRAL CONDUCTORS. ART250.119
RSLV 10/17/2014 10/17/2014 11/12/2014
 
003 (999) OTHER
MULTI WIRE CIRCUITS MEANS OF DISCONNECT NOT SIMULTANEOUS ART 210.4(BMULTI WIRE CIRCUITS NOT GROUPED 210.4(D)
RSLV 10/17/2014 10/17/2014 11/12/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back