BIS Menu  |  Bldg Info Search  |  Insp. Results  |  Certs. Occupancy  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B383241
Premises: 112 MANHATTAN AVENUE BROOKLYN BIN: 3071277     Block: 3070   Lot: 7
   
Application Completed and Certified

Filed: 112 MANHATTAN AV Census Tract:   505
THROUGHOUT Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11206 Community Board:   301
Related Job Number:    320690230
DOB Cross Street(s):   BOERUM STREET,    JOHNSON AVENUE
Status:   C - JOB IS SIGNED OFF 05/30/2015 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/10/2014 Job Start Date:   07/20/2014
Last Change:   05/30/2015 Job End Date:   07/20/2015
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     02/24/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009968 Licensee Name: SIGMOND FRIED
Firm: 000558 Firm Name: FRIED ELECTRIC CO.
Firm Phone: 718-389-2141  Firm Address: 67 WEST STREET, UNIT 321 BROOKLYN NY 11222 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $696.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320690230
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: AVRAHAM FISHER
Owner Business Name: 112 REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  10  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  15  30    15  15         
001  15  30    15  15         
002  10  25    10  10         
002  10  25    10  10         
003  10  25    10  10         
003  10  25    10  10         
004  10  25    10  10         
004  10  25    10  10         
005  10  15  30    15  15         
005  15  30    15  15         
Buildings Total 120  270    120  120     24           
Total Units : 654 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 11 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 11 - Removed Meters 3 = Total Meters 11

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/10/2014 Notice: 1 - FIRST NOTICE 01/26/2015
Power Issued: 07/10/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B383241
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/26/2014 12/01/2014 CCH V E (50) (9) Y
INSPECTION COMMENTS: JOB NOT COMPLETED (TOTAL INSPECTION)
 
(2) 12/22/2014 12/30/2014 CJH H X E (20) (0) Y
INSPECTION COMMENTS: JOB NOT COMPLETED THROUGHOUT
 
(3) 01/08/2015 01/13/2015 CCH A R E (90) (4) Y
INSPECTION COMMENTS: N
 
(4) 01/20/2015 01/26/2015 EBA A R E (60) (3) Y
INSPECTION COMMENTS: N
 
(5) 02/24/2015 02/26/2015 CCH C R E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B383241
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
END BOX FEEDERS IN HOLLOW SPACE (230.43)
RSLV 11/26/2014 12/22/2014 01/08/2015
 
002 (999) OTHER
PANELS CLEARANCE APT (110.26)(A)
RSLV 11/26/2014 12/22/2014 01/08/2015
 
003 (999) OTHER
PLP OVER 6'7 (404.8)
RSLV 11/26/2014 12/22/2014 01/08/2015
 
004 ( 19) DEFECTIVE WIRING IS IN USE
PLP NO BUSHING WIRES TRIP BRAKER
RSLV 11/26/2014 12/22/2014 01/08/2015
 
005 (999) OTHER
NO ACCESS PORT TO JUMP GROUNDING (314.29)
RSLV 11/26/2014 12/22/2014 01/08/2015
 
006 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
OUTSIDE PANCAKE BOX EXPOSED
RSLV 11/26/2014 12/22/2014 01/08/2015
 
007 (999) OTHER
SER SW TO CLOSE TO WALL NOT PENING PROPERLY (110.26)
RSLV 11/26/2014 12/22/2014 01/08/2015
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BLOWER IN BASEMENT IN SJ CORD
RSLV 11/26/2014 12/22/2014 01/08/2015
 
009 (999) OTHER
CIR NOT GROUPED (300.20) THROUGHOUT
RSLV 11/26/2014 12/22/2014 01/08/2015
 
010 (999) OTHER
NO ACCESS TO BOX WITH PIPE ON ROOF 314.29
RSLV 01/08/2015 01/08/2015 01/20/2015
 
011 ( 53) GFCI HAS NOT BEEN PROVIDED
ALL CT OUTLETS NOT GFCI PROTECTED
RSLV 01/08/2015 01/08/2015 01/20/2015
 
012 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
ALL OUTLETS CT BATHROOM SHEET ROCK SCREW
RSLV 01/08/2015 01/08/2015 01/20/2015
 
013 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
8FIXTURE MISSING TOP FL HALLWAY
RSLV 01/08/2015 01/08/2015 01/20/2015
 
014 (999) OTHER
NO DISCONNECT TO PROVIDED FOR SPLIT UNIT BLOWERS (430.75)
RSLV 01/20/2015 01/20/2015 02/24/2015
 
015 (999) OTHER
#14 WIRES USED TO FEED AC BLOWERS N.Y.C AMENDMENT
RSLV 01/20/2015 01/20/2015 02/24/2015
 
016 (999) OTHER
WIRES SMALLER THAN #4 REIDENTIFIED.(SPLICE BOX REAR A/C CONDENSER)(200.7)(C1)
RSLV 01/20/2015 01/20/2015 02/24/2015