| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
10 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
10 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER END BOX FEEDERS IN HOLLOW SPACE (230.43) |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 002 |
(999) |
OTHER PANELS CLEARANCE APT (110.26)(A) |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 003 |
(999) |
OTHER PLP OVER 6'7 (404.8) |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 004 |
( 19) |
DEFECTIVE WIRING IS IN USE PLP NO BUSHING WIRES TRIP BRAKER |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 005 |
(999) |
OTHER NO ACCESS PORT TO JUMP GROUNDING (314.29) |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 006 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE OUTSIDE PANCAKE BOX EXPOSED |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 007 |
(999) |
OTHER SER SW TO CLOSE TO WALL NOT PENING PROPERLY (110.26) |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 008 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BLOWER IN BASEMENT IN SJ CORD |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 009 |
(999) |
OTHER CIR NOT GROUPED (300.20) THROUGHOUT |
RSLV |
11/26/2014 |
12/22/2014 |
01/08/2015 |
| |
| 010 |
(999) |
OTHER NO ACCESS TO BOX WITH PIPE ON ROOF 314.29 |
RSLV |
01/08/2015 |
01/08/2015 |
01/20/2015 |
| |
| 011 |
( 53) |
GFCI HAS NOT BEEN PROVIDED ALL CT OUTLETS NOT GFCI PROTECTED |
RSLV |
01/08/2015 |
01/08/2015 |
01/20/2015 |
| |
| 012 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE ALL OUTLETS CT BATHROOM SHEET ROCK SCREW |
RSLV |
01/08/2015 |
01/08/2015 |
01/20/2015 |
| |
| 013 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED 8FIXTURE MISSING TOP FL HALLWAY |
RSLV |
01/08/2015 |
01/08/2015 |
01/20/2015 |
| |
| 014 |
(999) |
OTHER NO DISCONNECT TO PROVIDED FOR SPLIT UNIT BLOWERS (430.75) |
RSLV |
01/20/2015 |
01/20/2015 |
02/24/2015 |
| |
| 015 |
(999) |
OTHER #14 WIRES USED TO FEED AC BLOWERS N.Y.C AMENDMENT |
RSLV |
01/20/2015 |
01/20/2015 |
02/24/2015 |
| |
| 016 |
(999) |
OTHER WIRES SMALLER THAN #4 REIDENTIFIED.(SPLICE BOX REAR A/C CONDENSER)(200.7)(C1) |
RSLV |
01/20/2015 |
01/20/2015 |
02/24/2015 |