| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
6 |
|
| B. Over #2 to 1/0 |
1 |
3#1/0 WIRE |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
6 |
12CIR PNL |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER SERVICE MIGB BONDING SCREW |
RSLV |
02/09/2015 |
02/09/2015 |
04/02/2015 |
| |
| 002 |
(999) |
OTHER NEUTRAL NOT BONDED 250.28 |
RSLV |
02/09/2015 |
02/09/2015 |
04/02/2015 |
| |
| 003 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE CHANGE LUG IN 200 A SER SW |
RSLV |
02/09/2015 |
04/02/2015 |
04/16/2015 |
| |
| 004 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED WATER GROUND NOT PROPERLY SECURE |
RSLV |
02/09/2015 |
04/02/2015 |
04/16/2015 |
| |
| 005 |
(999) |
OTHER NO UTILITY BAR |
RSLV |
02/09/2015 |
04/02/2015 |
04/16/2015 |
| |
| 006 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY NO PANEL DIR THROUGHOUT |
RSLV |
02/09/2015 |
02/09/2015 |
04/02/2015 |
| |
| 007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED NO MAIN IN PLP PANEL |
RSLV |
02/09/2015 |
04/02/2015 |
04/16/2015 |
| |
| 008 |
(999) |
OTHER CIR NOT GROUP 300.20 |
RSLV |
02/09/2015 |
02/09/2015 |
04/02/2015 |
| |
| 009 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER C.T NEAR STOVE MISSING OUTLET THROUGHOUT |
RSLV |
02/09/2015 |
02/09/2015 |
04/02/2015 |
| |
| 010 |
(999) |
OTHER C.T OUTLET IN BACK SPLASH 314.29 |
RSLV |
02/09/2015 |
02/09/2015 |
04/02/2015 |
| |
| 011 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER 3RD FL FT KITCHEN COUNTER TOP RECEPTACLE NOT SUFFICEINT |
RSLV |
04/02/2015 |
04/02/2015 |
04/16/2015 |
| |
| 012 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 2ND FL FT COUNTER TOP RECEPTACLE NOT GFCI PROTECTED |
RSLV |
04/02/2015 |
04/02/2015 |
04/16/2015 |
| |
| 013 |
( 19) |
DEFECTIVE WIRING IS IN USE 2ND FL FT BEDROOMS RECEPTACLES NOT WORKING |
RSLV |
04/02/2015 |
04/02/2015 |
04/16/2015 |