BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B382865
Premises: 1145 FULTON STREET BROOKLYN BIN: 3251624     Block: 1997   Lot: 43
   
Application Completed and Certified

Filed: 1147 FULTON ST Census Tract:   227 Health Area:  1300
BASEMENT / 2ND FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   303
Special Place Name:   BETTER HEALTH PHARMACY
DOB Cross Street(s):   CLAVER PLACE,    FRANKLIN AVENUE
Status:   C - JOB IS SIGNED OFF 11/05/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/30/2014 10:44 AM
Application Entered:   06/30/2014 Job Start Date:   07/01/2014
Last Change:   11/05/2014 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     10/07/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011368 Licensee Name: CHRISTOPHER J STABILE
Firm: 002791 Firm Name: STABILITY ELEC ENTERP INC
Firm Phone: 718-449-8800  Firm Address: 8762 20TH AVENUE BROOKLYN NY 11214-4804 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $244.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MOHAMMAD ISMAIL
Owner Business Name: BETTER HEALTH PHARMACY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  100A;2-2-POLE S/S&1-PANEL
B. 101 Up to 200 AMPS  1  150A, 30CKT. COMBO PANEL
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  #2 THHN; 3- S/E & 1- FDR.
B. Over #2 to 1/0  1  #1/0 THHN S/E CONDUCTORS
C. Over 1/0 to 250 MCM  1  #3/0 THHN S/E CONDUCTORS
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  100A, 20CKT APT SUB-PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  N/A                     
Buildings Total                       
Total Units : 2 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 2 #10-Wire 0
Existing Meters 4 + New Meters 4 - Removed Meters 4 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/30/2014 Notice: 1 - FIRST NOTICE 08/30/2014
Power Issued: 06/30/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CONTRACTOR #00581 THIS APP. IS FILED FOR 1-SUPPLEMENTAL, 208V/200A, 3-PHASE SERVICE. EXIST. SVC. IS A 208V/200A SYSTEM.SCOPE OF WORK INCLUDES: 1-8X8X6FT SVC. TROUGH;2- 7-JAW MTR PANS;1-150A,3-PHASE PANEL; 1-100A,3-PHASE PANEL;2- 5-JAW MTR PANS; 2-100A,2-POLE S/S; 1-100A,SUB-RISER & 1-100A,SUB-PANEL.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B382865
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/26/2014 08/30/2014 CCH A E (55) (4) Y
INSPECTION COMMENTS: N
 
(2) 10/07/2014 10/14/2014 DAH C R E (25) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B382865
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO WATER GROUND TO NEAR SER SW
RSLV 08/26/2014 08/26/2014 10/07/2014
 
002 (999) OTHER
UTILITY BAR USE AS CALBARATOR BAR 250.64 F3
RSLV 08/26/2014 08/26/2014 10/07/2014
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
OUTLET NOT GFCI NEAR SERVICE
RSLV 08/26/2014 08/26/2014 10/07/2014
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
CHASE NIPPLE USE IN METER TO SER SW
RSLV 08/26/2014 08/26/2014 10/07/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.