BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B382591
Premises: 1800 AVENUE L BROOKLYN BIN: 3180696     Block: 6738   Lot: 1
   
Application Completed and Certified

Filed: 1800 AV L Census Tract:   538 Health Area:  7310
BASEMENT,1ST-6TH Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11230 Community Board:   314
DOB Cross Street(s):   EAST 18 STREET,    EAST 19 STREET
Status:   C - JOB IS SIGNED OFF 01/24/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/24/2014 8:02 AM
Application Entered:   06/24/2014 Job Start Date:   06/24/2014
Last Change:   01/24/2015 Job End Date:   12/25/2014
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     01/13/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011063 Licensee Name: MELVIN A BRANDL
Firm: 000219 Firm Name: BRANDL ELECTRIC INC.
Firm Phone: 718-327-5677  Firm Address: 71-34 MAIN STREET FLUSHING NY 11367 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $2,064.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EDITH FRIED
Owner Business Name: 1800AVE L ASSOCIATES LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  400 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  48  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  48  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1-8    12                 
002  9-16    12                 
003  17-24    12                 
004      12                 
005      12                 
006      12                 
Buildings Total   72  36                    
Total Units : 108 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 48 #4-Wire 1 #10-Wire 0
Existing Meters 49 + New Meters 49 - Removed Meters 49 = Total Meters 49

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/24/2014 Notice: 1 - FIRST NOTICE 11/25/2014
Power Issued: 06/24/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B382591
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/18/2014 11/25/2014 CCH A E (115) (5) Y
INSPECTION COMMENTS: CHECK EMT RUN 360 BENDS
 
(2) 01/13/2015 01/21/2015 CJE C R E (55) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B382591
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A) NO LIGHT NEAR SERVICE SW 110.26.D
RSLV 11/18/2014 11/18/2014 01/13/2015
 
002 (999) OTHER
B) SER SW NEED CLEARANCE 100.26
RSLV 11/18/2014 11/18/2014 01/13/2015
 
003 (999) OTHER
C)GROUNDING RACEWAY NOT CONTINUOUS (NEAR METERS) 250.64
RSLV 11/18/2014 11/18/2014 01/13/2015
 
004 (999) OTHER
D) SER SWITCH WATER GROUND SPLICE 250.64C
RSLV 11/18/2014 11/18/2014 01/13/2015
 
005 (999) OTHER
E) NO UTILITY BAR 250.94
RSLV 11/18/2014 11/18/2014 01/13/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back