BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B382439
Premises: 81 TEN EYCK STREET BROOKLYN BIN: 3338219     Block: 2792   Lot: 16
   
Application Completed and Certified

Filed: 81 TEN EYCK ST Census Tract:   503 Health Area:  0700
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11206 Community Board:   301
DOB Cross Street(s):   LORIMER STREET,    LEONARD STREET
Status:   C - JOB IS SIGNED OFF 08/20/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/19/2014 12:08 AM
Application Entered:   06/19/2014 Job Start Date:   06/19/2014
Last Change:   08/20/2015 Job End Date:   06/01/2015
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     08/14/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012311 Licensee Name: MOSES ROSENBERGER
Firm: 004090 Firm Name: HIVOLTS ELECTRICAL INC
Firm Phone: 718-855-4346  Firm Address: 21 HERKIMER PLACE BROOKLYN NY 11216 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $1,349.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: FULL TIME MANAGEMENT
Authorized Representative:  JOEL WERTZBERGER
Relationship To Owner:   MANGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  2  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  28  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  27  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    42  38    18  42     
001    28  64    20  28     
002    35  31    22  35         
003    35  31    22  35         
004    26  38    14  26     
Buildings Total 166  202    96  166     15     12      
Total Units : 657 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 26 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 27 - Removed Meters 1 = Total Meters 27

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/19/2014 Notice: 1 - FIRST NOTICE 08/11/2015
Power Issued: 06/19/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B382439
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/05/2015 08/11/2015 EBA A G (90) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 08/14/2015 08/19/2015 CCH C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B382439
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
NO GROUND BAR 250.64
RSLV 08/05/2015 08/05/2015 08/14/2015
 
002 (999) OTHER
TELEPHONE AND LOW VOLTAGE SYSTEMS INSTALLED IN ELECTRICAL ROOM 830.133 E,126.30F2.BULL 119/110.26
RSLV 08/05/2015 08/05/2015 08/14/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back