| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200AMPS 3/0 WIRE |
| C. 201 Up to 600 AMPS |
1 |
400AMPS 500MCM |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
16 |
100AMPS #2 WIRE |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
200AMPS 3/0 WIRE |
| D. Over 250 MCM |
1 |
400AMPS 3/0 WIRE |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
16 |
20CIRCUIT PANEL |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
42 CIRCUIT PANEL |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
1 |
24 VOLT'S |
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER CELLAR SVC ROOM COMMUNICATION WIRES CABLES INSTALLED IN SVC 800.133 |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |
| |
| 002 |
( 12) |
SERVICE CONDUCTORS ARE NOT OF THE PROPER SIZE CELLAR SVC SWITCH FUSES DISAIMILAR 110.2 |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |
| |
| 003 |
(999) |
OTHER CELLAR PLP CKT NOT GROUPED 210.4D |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |
| |
| 004 |
(999) |
OTHER CELLAR SVC AREA COMMUNICATION BAR NOT INSTALLED 250.94 |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |
| |
| 005 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER CELLAR SVC SWITCHES WATER METER JUMPER 250.53 |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |
| |
| 006 |
(999) |
OTHER CELLAR FIRE PUMP DISCONNECT NOT MARKED 693.4 (3) |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |
| |
| 007 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION APT 2C 3C BATHROOM LUMINARIES 410.10 |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |
| |
| 008 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ROOF AC UNITS 250.112 |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |
| |
| 009 |
(236) |
OUTSIDE A/C DISCONNECT NOT ACCESSIBLE ROOF AC UNITS 440.14 |
RSLV |
09/16/2015 |
09/16/2015 |
10/19/2015 |