BIS Menu  |  Applications  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B381722
Premises: 525 GEORGIA AVENUE BROOKLYN BIN: 3085010     Block: 3821   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 525 GEORGIA AV Census Tract:   1126 Health Area:  6300
BSMT,1FL,2FL Admin Area:   B - BROOKLYN Inspection Area:   H
BROOKLYN, NY 11207 Community Board:   305
Special Place Name:   BROOKLYN
DOB Cross Street(s):   LIVONIA AVENUE,    RIVERDALE AVENUE
Status:   C - JOB IS SIGNED OFF 05/17/2023
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/02/2014 3:54 PM
Application Entered:   06/02/2014 Job Start Date:   06/09/2014
Last Change:   05/17/2023 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     05/16/2023      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  D - DON'T ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010809 Licensee Name: JOHN L RICKFORD
Firm: 002075 Firm Name: R.J.ELECTRICAL CONTRACTOR
Firm Phone: 718-949-5466  Firm Address: 201-11 LINDEN BLVD ST. ALBANS NY 11412 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $95.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FRANCIS GITTENS
Owner Business Name: NONE
Authorized Representative:  RICKFORD JOHN
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  5-PANELS WITH 100 A MAIN
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1-SET OF 3#1/0 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 0 #10-Wire 0
Existing Meters 4 + New Meters 1 - Removed Meters 0 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/02/2014 Notice: 1 - FIRST NOTICE 11/29/2014
Power Issued: 06/02/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADING METER SERVICE FROM 60 AMPS 110/208 VOLTS TO 100 AMPS 110/208 VOLTS AND ADD ONE (1) METER FOR PLP. NO OTHER WORK DONE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B381722
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/25/2014 11/29/2014 CJH A D (40) (5) Y
INSPECTION COMMENTS: N
 
(2) 05/16/2023 05/17/2023 ECH C R (1) (0)
INSPECTION COMMENTS: SEE SUPERSEDING PERMIT B08048470

OBJECTION FOR APPLICATION #: B381722
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (279) WATER METER JUMPER IS MISSING/IMPROPER
(ALL FLOORS) CELLAR WATER METER JUMPER (250.53)
RSLV 11/25/2014 11/25/2014 05/16/2023
 
002 (999) OTHER
(ALL FLOORS)CELLAR SVC SWITCHES AND ELECTRODE NOT PER ART (250.64)(F3)
RSLV 11/25/2014 11/25/2014 05/16/2023
 
003 (999) OTHER
(ALL FLOORS) CELLAR AND RACEWAY NOT CONTINUOUS (250.64)(E)
RSLV 11/25/2014 11/25/2014 05/16/2023
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) CELLAR PNL OLD #14 ON 20A BRAKER (240.3)
RSLV 11/25/2014 11/25/2014 05/16/2023
 
005 (999) OTHER
(ALL FLOORS) CELLAR SVC SWITCHES BONDED CONDUCTOR UNDERSIZE (250.66)
RSLV 11/25/2014 11/25/2014 05/16/2023



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.