| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
4 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
4 |
3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
4-42CIR |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
1-HYDAULIC |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 002) PANEL MISSING KO. (ART 210 .12.A) |
RSLV |
08/30/2017 |
08/30/2017 |
11/20/2017 |
| |
| 002 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (ALL FLOORS)THROUGHOUT RECEPTACLES ARE NOT PROPERLY GROUNDED (ART 250.146) |
RSLV |
08/30/2017 |
08/30/2017 |
11/20/2017 |
| |
| 003 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS)THROUGHOUT REQUIRED CKT ARE NOT AFCI PROTECTED. (ART 210.12B) |
RSLV |
08/30/2017 |
08/30/2017 |
12/20/2017 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS) THROUGHOUT RECEPTACLE ARE NOT TR TYPE. (ART 406.11) |
RSLV |
08/30/2017 |
08/30/2017 |
11/20/2017 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) OUTDOOR RECEPTACLES ARE NOT WR TR TYPE (406.8 A &B) B. |
RSLV |
08/30/2017 |
08/30/2017 |
12/20/2017 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)KITCHEN GFCI RECEPTACLE BOX SETBACK IS MORE THAN 1/4" (ART 314.20) |
RSLV |
08/30/2017 |
08/30/2017 |
12/20/2017 |
| |
| 007 |
(999) |
OTHER (BASEMENT) WATER METER JUMPER IS NOT INSTALLED PROPERLY (ART 250.53) |
RSLV |
08/30/2017 |
08/30/2017 |
12/20/2017 |
| |
| 008 |
(999) |
OTHER (BASEMENT) CAB AND ELEV. DISCONNECT SWITCH HAS NEUTRAL BONDED. |
RSLV |
12/20/2017 |
12/20/2017 |
12/28/2017 |
| |
| 009 |
(999) |
OTHER (BASEMENT) CAB AND ELEV SWITCH HAS DOUBLE LUG. |
RSLV |
12/20/2017 |
12/20/2017 |
12/28/2017 |