BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B380898
Premises: 461 DEAN STREET BROOKLYN BIN: 3398591     Block: 1118   Lot: 2
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 461 DEAN ST Census Tract:   129.02
FLOORS 2 THRU 35 Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11217 Community Board:   306
Special Place Name:   ATLANTIC YARDS B2 MODULAR
Related Job Number:    320321139
DOB Cross Street(s):   FLATBUSH AVENUE,    6 AVENUE
Status:   C - JOB IS SIGNED OFF 03/08/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/12/2014 Job Start Date:   04/25/2014
Last Change:   03/08/2018 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   SEVERIANO JOHN       On     02/22/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011289 Licensee Name: PETER BORDUCCI
Firm: 002860 Firm Name: SOLAR ELEC. SYSTEMS, INC.
Firm Phone: 718-824-7000  Firm Address: 1402 BLONDELL AVENUE BRONX NY 10461 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320321139
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52291     Submittal #: 13A0686  
Owner / Occup: ROBERT SANNA
Owner Business Name: AYDC INTERIM DEVELOPER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  4  2-800A, 2-1200A
E. Over 1200 AMPS  6  3-1600A, 2-2000A, 1-3000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  14  4-500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  363  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  14  9-100A, 4-200A, 1-125A
D. 3 Phase Over 225 AMPS  1  1-800A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  5  3-100A, 1-150A, 1-200A
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    81  250  27  27  81             
003    81  250  27  27  81             
004    81  250  27  27  81             
005    108  331  36  36  108  45         
006    117  358  39  46  117             
007    147  391  39  50  147             
008    154  390  39  47  154             
009    174  375  39  51  174             
010    141  380  39  42  141  12  20         
011    199  386  39  50  199             
012    153  459  51  51  153             
013    153  459  51  51  153             
014    153  459  51  51  153             
015    153  459  51  51  153             
016    153  459  51  51  153             
017    153  459  51  51  153             
018    153  459  51  51  153             
019    144  432  48  64  144             
020    109  315  33  49  99             
021    108  324  36  48  108             
022    99  297  33  44  99             
023    108  324  36  48  108             
024    42  189  14  35  42             
025    42  189  14  35  42             
026    42  189  14  35  42             
027    42  189  14  35  42             
028    42  189  14  35  42             
029    42  189  14  35  42             
030    42  189  14  35  42             
031    42  189  14  35  42             
032    77  286  22  66  77             
033    24  19    24  11      30 
034    19    19  52     
035              22         
Buildings Total 3378  10091  1028  1367  3368     150        30 
Total Units : 19418 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 364 #4-Wire 1 #10-Wire 4
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/12/2014 Notice: 1 - FIRST NOTICE 11/03/2017
Power Issued: 05/12/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL BRANCH WIRING, LIGHTING, POWER & SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B380898
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/25/2017 08/25/2017 EBA V (240) (4)
INSPECTION COMMENTS: FAIL
 
(2) 11/02/2017 11/03/2017 CJH V Y (40) (1)
INSPECTION COMMENTS: FAIL
 
(3) 02/22/2018 02/22/2018 SVJ C R (1) (0)
INSPECTION COMMENTS: OK, SEE DOCUMENTS

OBJECTION FOR APPLICATION #: B380898
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) PANELS, MULTI CIRCUITS NOT GROUPED 210.4.D.
RSLV 08/25/2017 08/25/2017 02/22/2018
 
002 (999) OTHER
(ALL FLOORS) SOME GFI BREAKERS USED AS AFCI 210.12.B.
RSLV 08/25/2017 08/25/2017 11/02/2017
 
003 (999) OTHER
(ALL FLOORS) TERRACES, BUBBLE COVER, 406.8.B.
RSLV 08/25/2017 08/25/2017 11/02/2017
 
004 (999) OTHER
(ROOF) CAB LIGHTS NEUTRAL FUSED 240.22
RSLV 08/25/2017 08/25/2017 11/02/2017
 
005 (999) OTHER
(ALL FLOORS) TERRACE RECEPT OUTLETS NOT WR LISTED 406.8
RSLV 11/02/2017 11/02/2017 02/22/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.