| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
5 |
#6 WIRE |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
5 |
60 AMPS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER RISERS DOUBLE LUGGED IN BSMT 110.14A |
RSLV |
02/23/2015 |
02/23/2015 |
03/11/2015 |
| |
| 002 |
(999) |
OTHER NO AFCI PROTECTION FOR LIGHT RECEPT SMOKE ALARMS ALL PANELS 210.12B |
RSLV |
02/23/2015 |
02/23/2015 |
03/11/2015 |
| |
| 003 |
(999) |
OTHER MULTI CIRCUITS NEEDS TO BE DISCONNECTED SIMUTANEOUSLY ALL PANELS PLP210.4.B |
RSLV |
02/23/2015 |
02/23/2015 |
03/11/2015 |
| |
| 004 |
(999) |
OTHER MC CABLE NOT PROPERLY TERMINATED 250.146 |
RSLV |
02/23/2015 |
02/23/2015 |
03/11/2015 |
| |
| 005 |
(999) |
OTHER LOAD CALCULATION NEEDED FOR 40 AMP A/C AND HEATING UNITS |
RSLV |
02/23/2015 |
02/23/2015 |
03/11/2015 |
| |
| 006 |
(999) |
OTHER AFCI FOR LIGHTS AND SMOKE DETECTOR 210.12.B |
RSLV |
03/11/2015 |
03/11/2015 |
03/24/2015 |
| |
| 007 |
(999) |
OTHER MC CABLE NOT PROPERLY TERMINATED BOX,250.146 |
RSLV |
03/11/2015 |
03/11/2015 |
03/24/2015 |
| |
| 008 |
(999) |
OTHER LOW VOLTAGE SYSTEM IN ELECTRICAL ROOM 830.133,110.26 |
RSLV |
03/11/2015 |
03/11/2015 |
03/24/2015 |
| |
| 009 |
(999) |
OTHER PLP PANEL OVERFUSED 240.3 |
RSLV |
03/11/2015 |
03/11/2015 |
03/24/2015 |