Electrical Application Details for App #: B379822
Premises: 24 MAIN STREET BROOKLYN BIN: 3335867     Block: 36   Lot: 7501
   
Application Completed and Certified

Filed: 30 MAIN ST Census Tract:   21
BSMT Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Special Place Name:   BSMT
DOB Cross Street(s):   WATER STREET,    HOWARD ALLEY
Status:   C - JOB IS SIGNED OFF 05/29/2015
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/11/2014 Job Start Date:   04/11/2014
Last Change:   05/29/2015 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     05/12/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009586 Licensee Name: JEROME KONSKER
Firm: 000835 Firm Name: KONSKER ELECTRIC CORP.
Firm Phone: 718-721-1122  Firm Address: 68-05 FRESH MEADOW LANE, STE #3 FRESH MEADOW NY 11365 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
Total Fee:  $3,960.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52222     Submittal #: 14A0049  
Owner / Occup: JEREMY ISENBERG
Owner Business Name: SWEENEY CONDOMINIUM
Authorized Representative:  JEROME KONSKER
Relationship To Owner:   AUTHORIZED REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  100AMP,#4WIRE/FIREPUMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  1-3000 AMP,1-2500 AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  32  600 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  1-200 AMP,1-100 AMP
D. 3 Phase Over 225 AMPS  3  MDP AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  2 SETS 350 MCM
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS      15      300 
Buildings Total      15          300 
Total Units : 328 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/11/2014 Notice: 1 - FIRST NOTICE 01/21/2015
Power Issued: 04/11/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPAIR ELECTRICAL SERVICE DUE TO HURRICANE SANDY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B379822
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/15/2015 01/21/2015 HRB V D (170) (12) Y
INSPECTION COMMENTS: NEED TO REINSPECT AFTER ADVISORY BOARD DRAWING ARE REDONE
 
(2) 03/13/2015 03/17/2015 EBA J Y E (30) (0) Y
INSPECTION COMMENTS: VIOLATIONS PARTLY REMOVED
 
(3) 04/20/2015 04/27/2015 HRB J Y E (40) (0) Y
INSPECTION COMMENTS: N
 
(4) 05/12/2015 05/18/2015 HRB C R E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B379822
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT ROOM DRAWINGS, ONE LINE DRAWINGS NOT AS APPROVE DRAWINGS(110.2)(B)
RSLV 01/15/2015 04/20/2015 05/12/2015
 
002 (999) OTHER
BASEMENT 277/480 RACEWAYS NOT BONDED (250.97)
RSLV 01/15/2015 04/20/2015 05/12/2015
 
003 (999) OTHER
BASEMENT INCOMING RACEWAYS NOT BONDED (250.92)
RSLV 01/15/2015 03/13/2015 04/20/2015
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
BASEMENT OUTLETS IN SERVICE ROOM
RSLV 01/15/2015 01/15/2015 03/13/2015
 
005 (999) OTHER
BASEMENT FUSES ARE NOT AS PER DRAWINGS (110.2)(B)
RSLV 01/15/2015 03/13/2015 04/20/2015
 
006 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT INSIDE LIGHTING PANEL
RSLV 01/15/2015 03/13/2015 04/20/2015
 
007 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BASEMENT INSIDE LIGHTING PANEL
RSLV 01/15/2015 04/20/2015 05/12/2015
 
008 (999) OTHER
BASEMENT MISSING PANIC BARS FOR DOORS (110.26)(2)
RSLV 01/15/2015 01/15/2015 03/13/2015
 
009 (999) OTHER
BASEMENT NEED UTILITY GROUNDING BAR (250.94)
RSLV 01/15/2015 03/13/2015 04/20/2015
 
010 (999) OTHER
BASEMENT GROUND ROD NOT CONNECTED TO GROUNDING BAR (250.64)(D)
RSLV 01/15/2015 03/13/2015 04/20/2015
 
011 (999) OTHER
BASEMENT INCOMING RACEWAY NOT SEALED (230.8)
RSLV 01/15/2015 04/20/2015 05/12/2015
 
012 (999) OTHER
BASEMENT WATER METER JUMPER OXIDATIONING
RSLV 01/15/2015 03/13/2015 04/20/2015