BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B379580
Premises: 9201 SHORE ROAD BROOKLYN BIN: 3331025     Block: 6099   Lot: 13
   
Application Completed and Certified

Filed: 9201 SHORE RD Census Tract:   52.02 Health Area:  7810
ELEVATOR MACHINE ROOM & PIT Admin Area:   B - BROOKLYN Inspection Area:   S
BROOKLYN, NY 11209 Community Board:   310
DOB Cross Street(s):    92 STREET,    92 STREET PEDESTRIAN OVERPASS
Status:   C - JOB IS SIGNED OFF 06/11/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/07/2014 9:15 AM
Application Entered:   04/07/2014 Job Start Date:   04/07/2014
Last Change:   06/11/2015 Job End Date:   04/07/2015
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     05/21/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012128 Licensee Name: JOHN DICAPUA
Firm: 003833 Firm Name: CAPUTEK ELEC'L SERVICES,
Firm Phone: 718-610-9299  Firm Address: 1460 BROADWAY, 7TH FLOOR INC NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $540.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   D4-ELEVATOR APT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: FIRST SERVICE RESIDENTIAL
Authorized Representative:  STEVE HYATT
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  3P5320,21,22,23
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/02/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MODERNIZATION OF (4) FOUR DEVICES #S, 3P5320,3P5321,3P5322,3P5323

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B379580
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/29/2015 02/02/2015 CJH A (90) (4) Y
INSPECTION COMMENTS: N
 
(2) 05/21/2015 05/28/2015 JTE C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: B379580
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ROOF ELEVATORS DIS SWITCH CONDUCTORS NOT GROUPED 300.3 (B)
RSLV 01/29/2015 01/29/2015 05/21/2015
 
002 (999) OTHER
ROOF ELEVATOR RM CAR DIS SWITCHES DOUBLE LUGGING 110.14
RSLV 01/29/2015 01/29/2015 05/21/2015
 
003 (999) OTHER
ROOF A CAR DIS SWITCHES BUSHING LOCKNUTS MISSING 300.11
RSLV 01/29/2015 01/29/2015 05/21/2015
 
004 (999) OTHER
ROOF A CAR DIS SWITCHES #14 CONDUCTORS IN USE 210.19 A4
RSLV 01/29/2015 01/29/2015 05/21/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back