| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BASE - SERVICE NEUTRAL NOT GROUPED. 250.24(C) |
RSLV |
07/14/2014 |
07/14/2014 |
02/05/2015 |
| |
| 002 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE BASE - NEITRAL NOT BONDED. ART 250.28 |
RSLV |
07/14/2014 |
07/14/2014 |
02/05/2015 |
| |
| 003 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED BASE - ILLUMINATION OF SERVICE EQUIPEMENT NOT SUFFICIENT 110.26(D) |
RSLV |
07/14/2014 |
07/14/2014 |
02/05/2015 |
| |
| 004 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE BASE METER BANK TAP 300.11 |
RSLV |
02/05/2015 |
02/05/2015 |
03/09/2015 |
| |
| 005 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH 200 AMPS DISCONNECT SWITCH |
RSLV |
02/05/2015 |
02/05/2015 |
03/09/2015 |
| |
| 006 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH CELLAR PULL BOX 110.14 (A) |
RSLV |
03/09/2015 |
03/09/2015 |
07/28/2015 |
| |
| 007 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (ALL FLOORS) CELLAR TO FIFTH FLOOR FEEDER CONDUCTOR 310.4C |
RSLV |
03/09/2015 |
07/28/2015 |
02/05/2016 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS) APT 5B 5C NEED LOAD CALCULATIONB 220.12 |
RSLV |
03/09/2015 |
07/28/2015 |
02/05/2016 |