| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
1 SET OF 4#1'S ELEVATOR |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
1 |
400AMP 42 CKT |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT NO RECEPTACLE OUTSIDE NEAR AC UNITS (ART 210.63) |
RSLV |
03/17/2015 |
03/17/2015 |
04/23/2015 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED BASEMENT MISSING CONDULET CONVER IN BOILER ROOM FOR SMALLER OUTSIDEAC UNIT (ART 314.25) |
RSLV |
03/17/2015 |
03/17/2015 |
04/23/2015 |
| |
| 003 |
(999) |
OTHER BASEMENT 400 PANEL IN PANTRY MULTI WIRE CIRCUITS MEANS OF DISCONNECTNOT SIMULTANEOUS (ART 210.4)(B) |
RSLV |
03/17/2015 |
03/17/2015 |
04/23/2015 |
| |
| 004 |
(999) |
OTHER BASE MULTI WIRE CIRCUITS IN PANTRY 400AMP PANEL CIRCUITS NOT GROUPED(ART 210.4)(D) |
RSLV |
03/17/2015 |
03/17/2015 |
04/23/2015 |
| |
| 005 |
(999) |
OTHER SER ROOM MULTI WIRE CIRCUITS IN B-PP-3 PANEL MEANS OF DISCONNECT NOTSIMULTANEOUS (ART 210.4)(B) |
RSLV |
03/17/2015 |
03/17/2015 |
04/23/2015 |
| |
| 006 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY BASE NO PANEL DIRECTORY IN PANTRY PANEL & SER ROOM PANELS (ART 408.4) |
RSLV |
03/17/2015 |
03/17/2015 |
04/23/2015 |
| |
| 007 |
(151) |
AIR COND/REFRIG EQUIPMENT NOT PROPERLY MARKED/SIZED/INSTALLED OUTSIDE AC NOT PROPERLY MARKED OUTSIDE |
RSLV |
03/17/2015 |
03/17/2015 |
04/23/2015 |