| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
4 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
3#2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
4# 3/0 |
| D. Over 250 MCM |
2 |
4#500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
42 CKT |
| D. 3 Phase Over 225 AMPS |
1 |
42 CKT |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER SERVICE IN HOLLOW FRAME 230.43 |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 002 |
(999) |
OTHER 12X3 NOT ON TIE BRAKER 210.4 |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 003 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER A MIGB MISSING BONDING SCREW |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 004 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER B MIGB NOT BONDED TO SCREW |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 005 |
( 11) |
FEEDER CONDUCTORS ARE NOT OF PROPER SIZE METER NIPPLE NOT BONDED TROUGH |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 006 |
(999) |
OTHER CIR NOT GROUP BSMT 300.20 |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 007 |
(999) |
OTHER NO UTILITY BAR 250.94 |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 008 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY NO WATER GROUND NOT AT ALL SERVICE SWS |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 009 |
(999) |
OTHER HOOD RACEWAY INSIDE TO LIGHT 410.10C |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 010 |
( 53) |
GFCI HAS NOT BEEN PROVIDED KITCHEN OUTLET NOT GFCI |
RSLV |
10/24/2014 |
10/24/2014 |
11/17/2014 |
| |
| 011 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BASEMENT- NOT PROPERLY INSTALL GROUND WIRE LOOP THROUGH SWS |
RSLV |
11/17/2014 |
11/17/2014 |
12/05/2014 |