BIS Menu  |  Plumb. Inspections  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B378142
Premises: 212 GREENE AVENUE BROOKLYN BIN: 3056213     Block: 1965   Lot: 37
   
Application Completed and Certified

Filed: 212 GREENE AV Census Tract:   201 Health Area:  1300
RESTAURANT MAIN FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   302
Special Place Name:   RESTAURANT MAIN FLOOR
DOB Cross Street(s):   CAMBRIDGE PLACE,    GRAND AVENUE
Status:   C - JOB IS SIGNED OFF 03/10/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/01/2014 12:03 PM
Application Entered:   03/01/2014 Job Start Date:   03/05/2014
Last Change:   03/10/2015 Job End Date:   05/30/2014
Appointment Status:   
Last Inspection By:   WEISBART, F.       On     12/05/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009860 Licensee Name: JOSEPH TODARO
Firm: 002632 Firm Name: TNT ELECTRIC CO., INC.
Firm Phone: 347-763-2342  Firm Address: 41 BOX STREET, STE 301 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $428.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM J CLINTON
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4# 3/0
D. Over 250 MCM  2  4#500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  42 CKT
D. 3 Phase Over 225 AMPS  1  42 CKT
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  STORE  30  25    10  30             
Buildings Total 30  25    10  30                
Total Units : 95 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 1
Existing Meters 5 + New Meters 5 - Removed Meters 5 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/01/2014 Notice: 1 - FIRST NOTICE 11/26/2014
Power Issued: 03/01/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RESTAURANT MAIN FLOOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B378142
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/24/2014 10/27/2014 CCH V E (60) (10) Y
INSPECTION COMMENTS: NO ACCESS TO ROOF AC UNIT AND FAN
 
(2) 11/17/2014 11/26/2014 CCH A R E (55) (1) Y
INSPECTION COMMENTS: -
 
(3) 12/05/2014 12/05/2014 FWE C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B378142
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
SERVICE IN HOLLOW FRAME 230.43
RSLV 10/24/2014 10/24/2014 11/17/2014
 
002 (999) OTHER
12X3 NOT ON TIE BRAKER 210.4
RSLV 10/24/2014 10/24/2014 11/17/2014
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
A MIGB MISSING BONDING SCREW
RSLV 10/24/2014 10/24/2014 11/17/2014
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
B MIGB NOT BONDED TO SCREW
RSLV 10/24/2014 10/24/2014 11/17/2014
 
005 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
METER NIPPLE NOT BONDED TROUGH
RSLV 10/24/2014 10/24/2014 11/17/2014
 
006 (999) OTHER
CIR NOT GROUP BSMT 300.20
RSLV 10/24/2014 10/24/2014 11/17/2014
 
007 (999) OTHER
NO UTILITY BAR 250.94
RSLV 10/24/2014 10/24/2014 11/17/2014
 
008 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO WATER GROUND NOT AT ALL SERVICE SWS
RSLV 10/24/2014 10/24/2014 11/17/2014
 
009 (999) OTHER
HOOD RACEWAY INSIDE TO LIGHT 410.10C
RSLV 10/24/2014 10/24/2014 11/17/2014
 
010 ( 53) GFCI HAS NOT BEEN PROVIDED
KITCHEN OUTLET NOT GFCI
RSLV 10/24/2014 10/24/2014 11/17/2014
 
011 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASEMENT- NOT PROPERLY INSTALL GROUND WIRE LOOP THROUGH SWS
RSLV 11/17/2014 11/17/2014 12/05/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.