BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B377926
Premises: 255 WATER STREET BROOKLYN BIN: 3000055     Block: 32   Lot: 55
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 247 WATER ST Census Tract:   21 Health Area:  1000
ELEVATOR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   BRIDGE STREET,    GOLD STREET
Status:   C - JOB IS SIGNED OFF 07/24/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/24/2014 1:50 PM
Application Entered:   02/24/2014 Job Start Date:   02/24/2014
Last Change:   07/24/2020 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   PORAZZO, P       On     07/24/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011101 Licensee Name: JOSHUA GUTTMAN
Firm: 001557 Firm Name: ZEV ELECTRIC CORP.
Firm Phone: 718-522-1267  Firm Address: 202 PLYMOUTH STREET 1ST FLR BROOKLYN NY 11201 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $180.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JACK GUTTMAN
Owner Business Name: 255 WATER ASSOC. LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET OF 4 #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  SERVES FLOORS 1-5
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/14/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B377926
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/14/2020 07/14/2020 JGX V (53) (2)
INSPECTION COMMENTS: INSPECTION COMPLETED. CONTACT - EPHRAIM HERSKOVITZ (347)219-3109. REP VERIFIED FROM OFFICE THAT THIS APP RELATED TO ELEV #1 - ID # 3P14693. 2 OBJECTIONS ISSUED. CONTRACTOR TO SELF-CERTIFY.
 
(2) 07/24/2020 07/24/2020 PP1 J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000015424
 
(3) 07/24/2020 07/24/2020 PP1 C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000015423

OBJECTION FOR APPLICATION #: B377926
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
(ROOF)#8 WHITE USED AS PHASE CONDUCTOR BETWEEN SPLICE BOX AND ELEV #1 CABLIGHT DS. ART. 200.6
RSLV 07/14/2020 07/14/2020 07/24/2020
 
002 ( 61) INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS
(ROOF) EGC'S DOUBLE-LUGGED AT ELEV #1 SPLICE BOX. ART. 110.14.A
RSLV 07/14/2020 07/14/2020 07/24/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order