BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B377736
Premises: 736 EAST 3 STREET BROOKLYN BIN: 3127069     Block: 5396   Lot: 37
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 736 E 3 ST Census Tract:   484
GROUND FLOOR Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11218 Community Board:   312
DOB Cross Street(s):   DITMAS AVENUE,    AVENUE F
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   02/19/2014 Job Start Date:   01/15/2014
Last Change:   08/22/2025 Job End Date:   01/15/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     03/04/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  D - DON'T ISSUE POWER AUTH
Objection Disposition:  

License #: 012634 Licensee Name: MOISHE C KLEIN
Firm: 003748 Firm Name: CONTACT ELECTRIC CORP
Firm Phone: 718-438-4225  Firm Address: 1266 36TH STREET BROOKLYN NY 11218 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011135 POTCHIN, MOSHE 003748 CONTACT ELECTRIC CORP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $295.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANDREW WEBER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200AMP
C. 201 Up to 600 AMPS  1  400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  1  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 2 - Removed Meters 1 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 02/19/2014 Notice: 1 - FIRST NOTICE 03/17/2014
Power Issued: 02/19/2014 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B377736
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/04/2014 03/17/2014 CJE V D (30) (2) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B377736
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
GROUND RACEWAY TO GROUND ROD NOT CONTINUOUS, BOTH SIDR ART 250.64(C)
OPEN 03/04/2014 03/04/2014
 
002 (248) EACH OCCUPANT SHALL HAVE ACCESS
3RD FL OCCUPANT HAS NO ACCESS TO SERVICE DISCONNECING MEANS. ART230.72(C)
OPEN 03/04/2014 03/04/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.