BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B377691
Premises: 209 SMITH STREET BROOKLYN BIN: 3347506     Block: 403   Lot: 7504
   

Filed: 209 SMITH ST Census Tract:   69 Health Area:  2400
BASEMENT & FIRST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   306
DOB Cross Street(s):   BALTIC STREET,    BUTLER STREET
Status:   C - SIGNOFF IS AWAITING FEE PAYMENT 09/11/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/17/2014 9:07 PM
Application Entered:   02/17/2014 Job Start Date:   02/18/2014
Last Change:   09/11/2015 Job End Date:   02/18/2015
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     09/01/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010445 Licensee Name: GEORGE MOLLER
Firm: 003016 Firm Name: MOLLER & MOLLER INC.D/B/A
Firm Phone: 718-995-9400  Firm Address: 148-19 GUY R. BREWER BLVD MOLLER & MOLLER ELEC'L C JAMAICA NY 11434 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $45.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MANHATTAN CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    12                   
001    11                   
Buildings Total 23                      
Total Units : 31 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/11/2015 Notice: 1 - FIRST NOTICE 09/08/2014
Power Issued: 09/11/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B377691
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/04/2014 09/08/2014 CJE A (35) (3) Y
INSPECTION COMMENTS: N
 
(2) 09/01/2015 09/11/2015 DAH C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B377691
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
1ST FLOOR UNUSED OPENINGS FOR CIRCUIT BREAKERS NOT CLOSED ART 408.7
RSLV 09/04/2014 09/04/2014 09/01/2015
 
002 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BASEMENT ARMORED CABLE NOT PROPERLY SECURED. BX HANGING FROM CEILINGART 320.30
RSLV 09/04/2014 09/04/2014 09/01/2015
 
003 (999) OTHER
ALL FLUORESCENT FIXTURE NO QUICK DISCONNECTING MEANS. ART 410.130
RSLV 09/04/2014 09/04/2014 09/01/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.