| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
3 |
100 |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
45 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
45 |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER ALL OUTLETS NOT TAMPER PROOF 406.11 |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED SMOKE DETECTOR NO ARC FAULT |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 003 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS NO AC OUTLET LIVING ROOM |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 004 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE PIGTAIL IN US |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX KO MISSING SER SW END BOX |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 006 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) EMT TO END BOX NO STRAPP |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 007 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED METER NEUTRAL JUMPER NOT PROPER INSTALL ALL METERS |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 008 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER MIGB MISSING BONDING SCREW |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 009 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY GROUND NOT TO NEUTRAL BAR |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 010 |
(999) |
OTHER NEUTRAL BAR NOT BONDED 250.28 |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 011 |
( 10) |
BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE 20 AMP BREAKER ON OLD #14 WIRE |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 012 |
( 53) |
GFCI HAS NOT BEEN PROVIDED GFCI NOT INSTALLED IN BATHROOM |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 013 |
(999) |
OTHER NO GROUNDING TERMINAL INSTALL 250.64 F3 |
RSLV |
06/02/2014 |
06/02/2014 |
06/19/2014 |
| |
| 014 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY G.E.C. NOT CONNECTED TO NEUTRAL BAR IN SERVICE SWITCH ART 250.24(C) |
RSLV |
06/19/2014 |
06/19/2014 |
07/28/2014 |
| |
| 015 |
(231) |
NO OTHER OUTLET MICROWAVE RECEPTACLE + HOOD CONNECTED TO SMALL APPLIANCE COUNTERTOPCIRCUIT ART.210.52(B2) |
RSLV |
06/19/2014 |
06/19/2014 |
07/28/2014 |