BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B377493
Premises: 322 6 STREET BROOKLYN BIN: 3021599     Block: 993   Lot: 31
   
Application Completed and Certified

Filed: 322 SIXTH ST Census Tract:   137 Health Area:  4600
APT. 17 Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
Special Place Name:   4TH FL.
DOB Cross Street(s):    4 AVENUE,    5 AVENUE
Status:   C - JOB IS SIGNED OFF 07/30/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/11/2014 10:32 AM
Application Entered:   02/11/2014 Job Start Date:   02/15/2014
Last Change:   07/30/2014 Job End Date:   03/10/2014
Appointment Status:   
Last Inspection By:   BANYA, E       On     06/13/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010098 Licensee Name: JOHN E LONERGAN
Firm: 000885 Firm Name: JOHN E. LONERGAN
Firm Phone: 718-875-6100  Firm Address: 95 COURT STREET BROOKLYN NY 11201 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $109.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PHIL CRAMER
Owner Business Name: 322 6AVE OWNERS CO-OP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  30 CKT 100 AMP PANEL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  17    30  15  30             
Buildings Total   30  15  30                
Total Units : 78 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/28/2014 Notice: 1 - FIRST NOTICE 04/28/2014
Power Issued: 04/28/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B377493
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/10/2014 04/14/2014 DEX V (35) (5) Y
INSPECTION COMMENTS: NEED ACCESS TO BASEMENT TO CHECK FEEDER CONDUCTOR
 
(2) 04/23/2014 04/28/2014 CCH A R E (55) (6) Y
INSPECTION COMMENTS: N
 
(3) 05/06/2014 05/12/2014 EBA N (7) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELLED
 
(4) 05/20/2014 05/27/2014 CJE H Y (40) (0) Y
INSPECTION COMMENTS: N
 
(5) 06/13/2014 06/16/2014 EBA C R (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B377493
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
IN PANEL ALL (MC CABLE) GROUND WIRES NOT CONNECTED TO GROUND BAR TOENCLOSURE
RSLV 04/10/2014 04/10/2014 04/23/2014
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
KITCHEN COUNTERTOP NOT GFCI PROTECTED
RSLV 04/10/2014 04/10/2014 04/23/2014
 
003 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
APARTMENT HALLWAYS OUTLET
RSLV 04/10/2014 04/10/2014 04/23/2014
 
004 (999) OTHER
KITCHEN COUNTER TOP OVERHANG OVER (6") OUTLETS NOT REQUIRED 210.52C1
RSLV 04/10/2014 04/10/2014 04/23/2014
 
005 (999) OTHER
GFCI OUTLETS NOT TAMPER PROOF PROTECTED 406.11
RSLV 04/10/2014 04/10/2014 04/23/2014
 
006 (999) OTHER
A MC CABLE NOT CONNECTED TO BOXES 250.146
RSLV 04/23/2014 04/23/2014 05/20/2014
 
007 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
PANEL KO MISSING
RSLV 04/23/2014 04/23/2014 05/20/2014
 
008 (999) OTHER
B PANEL GROUNDING BAR NOT DRILL TAP 250.8 A3
RSLV 04/23/2014 04/23/2014 05/20/2014
 
009 (999) OTHER
C OUTLET BOXES 2 WIRES UNDER 1 SCREW 110.14A
RSLV 04/23/2014 04/23/2014 05/20/2014
 
010 (999) OTHER
D ALL OUTLET NOT TAMPER PROOF 406.11
RSLV 04/23/2014 04/23/2014 05/20/2014
 
011 ( 19) DEFECTIVE WIRING IS IN USE
12X3 ON SAME BREAKER
RSLV 04/23/2014 05/20/2014 06/13/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back