BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B377207
Premises: 801 PARK PLACE BROOKLYN BIN: 3330794     Block: 1233   Lot: 26
   
Application Completed and Certified

Filed: 760 PROSPECT PL Census Tract:   317.01 Health Area:  2900
BSMNT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11216 Community Board:   308
DOB Cross Street(s):   ROGERS AVENUE,    NOSTRAND AVENUE
Status:   C - JOB IS SIGNED OFF 11/17/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/31/2014 5:58 PM
Application Entered:   01/31/2014 Job Start Date:   02/03/2014
Last Change:   11/17/2014 Job End Date:   04/15/2014
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     11/13/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011422 Licensee Name: MICHAEL RIGLIETTI
Firm: 003360 Firm Name: MSR ELECTRICAL CONST CORP
Firm Phone: 718-743-2742  Firm Address: 2737 OCEAN AVENUE BROOKLYN NY 11229 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HOWIE WILDER
Owner Business Name: NYC SCA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  60AMP 20 BREAKERS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/20/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  60 AMP PANEL INSTALLED BEHIND AUDITORIUM

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B377207
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/29/2014 10/06/2014 CJH N (30) (0) Y
INSPECTION COMMENTS: N
 
(2) 10/16/2014 10/20/2014 CJH A (85) (4) Y
INSPECTION COMMENTS: N
 
(3) 11/13/2014 11/17/2014 CJE C R (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B377207
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CIRCUIT NOT GROUPED 210.4D
RSLV 10/16/2014 10/16/2014 11/13/2014
 
002 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
PNL FEEDERS CONDUCTOR 210.5
RSLV 10/16/2014 10/16/2014 11/13/2014
 
003 (999) OTHER
PNL EQUIPTMENT GND NOT MIN SIZE 250.122
RSLV 10/16/2014 10/16/2014 11/13/2014
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
CELLAR 1ST OPNL NOT LABEL 408.4
RSLV 10/16/2014 10/16/2014 11/13/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back