Electrical Application Details for App #: B376490
Premises: 1269 EAST 18 STREET BROOKLYN BIN: 3180707     Block: 6738   Lot: 40
   
Application Completed and Certified

Filed: 1269 E 18 ST Census Tract:   538
ALL FLOORS Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11230 Community Board:   314
DOB Cross Street(s):   AVENUE L,    BAY AVENUE
Status:   C - JOB IS SIGNED OFF 01/07/2015
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/14/2014 Job Start Date:   01/13/2014
Last Change:   01/07/2015 Job End Date:   01/01/2016
Appointment Status:   
Last Inspection By:   BEST, J       On     12/11/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011006 Licensee Name: YURY LESHCHINSKY
Firm: 003700 Firm Name: ENTERPRISE ELEC'L SYSTEMS
Firm Phone: 718-484-2151  Firm Address: 502 CONEY ISLAND AVE INC BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $2,077.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   A - ADEQUATE WIRING PROGRAM
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MORRIS LIBERMAN
Owner Business Name: 1269 EAST 18 ST RLTY LLC
Authorized Representative:  YURY LESHCINSKY
Relationship To Owner:   AUTHORIZED REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1 X 200 AMP
C. 201 Up to 600 AMPS  2  2 X 600 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  50  50 X APT RISERS 3#6,3#4
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  5  2 SETS 4#4/0,1X PLP 4#3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  50  50 X 100 AMP APT PANELS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1 X 200 AMP PLP PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      22                   
002      26                   
003      26                   
004      26                   
Buildings Total   100                      
Total Units : 100 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 50 #4-Wire 1 #10-Wire 0
Existing Meters 52 + New Meters 51 - Removed Meters 52 = Total Meters 51

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/14/2014 Notice: 1 - FIRST NOTICE 09/22/2014
Power Issued: 01/14/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B376490
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/17/2014 09/22/2014 CLC A E (90) (4) Y
INSPECTION COMMENTS: ACCESS TO APT A2 B11 C9 B12 D9 B1 C5 C4 D2 D1
 
(2) 12/11/2014 12/15/2014 JSB C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B376490
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
EMT NOT SUPPORTED SVC AREA CEILING
RSLV 09/17/2014 09/17/2014 12/11/2014
 
002 (999) OTHER
SVC GND RACEWAY NOT CONTINOUS TO WATER MAIN 250.64E
RSLV 09/17/2014 09/17/2014 12/11/2014
 
003 (999) OTHER
APT A2 OUTLETS INSTALLED NOT TR 406.11
RSLV 09/17/2014 09/17/2014 12/11/2014
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
METER BANK OVER FUSED AT 450 AMPS
RSLV 09/17/2014 09/17/2014 12/11/2014