| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
SUB-PANEL |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER LIGHT FIXTURES IN CEILING NOT SUPPORTED |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 002 |
(999) |
OTHER MC CABLE NOT BONDED TO BOX WALL CEILING 250.146 |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED GROUNDING TERMINAL INSTALLED IN PANEL |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 004 |
( 29) |
OUTLET BOXES ARE NOT COVERED OPEN BOXES IN CEILING |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 005 |
( 19) |
DEFECTIVE WIRING IS IN USE NO DIS SW ON FEEDERS |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 006 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED OUTLET NEAR BASEMENT DOOR NOT PROPERLY INSTALLED MC CABLE |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED FLOOR OUTLET NOT IN PROPER BOX |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 008 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER LIGHT FIXTURE IN CEILING NO SUPPORTED |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 009 |
(999) |
OTHER MC CABLE NOT BONDED TO BOX WALL CEILING 250.146 |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 010 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED GROUNDING TERMINAL ISOLATED IN PANEL |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 011 |
( 29) |
OUTLET BOXES ARE NOT COVERED OPEN BOXES IN CEILING |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 012 |
( 19) |
DEFECTIVE WIRING IS IN USE NO DIS SW ON FEEDERS |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 013 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED OUTLET NEAR BSMT DOOR NOT PROPERLY INSTALL MC CABLE |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 014 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED FLOOR OUTLET NOT IN PROPER BOX |
RSLV |
03/12/2014 |
03/12/2014 |
04/16/2014 |
| |
| 015 |
(999) |
OTHER A 200 AMP DIS SW NEUTRAL IS BONDED 250.24A |
RSLV |
04/16/2014 |
04/28/2014 |
05/29/2014 |
| |
| 016 |
( 40) |
LOCKNUTS ARE MISSING OR LOOSE 200 AMP DIS NO LOCK NUT ON NIPPLE |
RSLV |
04/16/2014 |
04/28/2014 |
05/29/2014 |
| |
| 017 |
( 41) |
LOCKNUTS ARE NOT MADE UP TIGHT 200 AMP DIS EMT NOT PROPERLY INSTALL |
RSLV |
04/16/2014 |
04/28/2014 |
05/29/2014 |
| |
| 018 |
(999) |
OTHER B MC CABLE NOT BONDED TO OUTLET THROUGHOUT CEILING 250.146 |
RSLV |
04/16/2014 |
04/28/2014 |
05/29/2014 |
| |
| 019 |
(999) |
OTHER C GROUNDING TERMINAL NOT PROPERLY INSTALL IN PANEL DRILL TAP 250.8.A |
RSLV |
04/16/2014 |
04/28/2014 |
05/29/2014 |
| |
| 020 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX OUTSIDE BOX MISSING KO |
RSLV |
04/16/2014 |
04/28/2014 |
05/29/2014 |