Electrical Application Details for App #: B375956
Premises: 207 ROCHESTER AVENUE BROOKLYN BIN: 3324639     Block: 1374   Lot: 7
   
Application Completed and Certified

Filed: 207 ROCHESTER AV Census Tract:   347 Health Area:  5020
GRND FLOOR 205&207 Admin Area:   B - BROOKLYN Inspection Area:   H
BROOKLYN, NY 11213 Community Board:   308
Special Place Name:   STERLING & PARK PL
Related Job Number:    320573866
DOB Cross Street(s):   PARK PLACE,    STERLING PLACE
Status:   C - JOB IS SIGNED OFF 06/18/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/23/2013 5:04 PM
Application Entered:   12/23/2013 Job Start Date:   12/23/2013
Last Change:   06/18/2014 Job End Date:   04/23/2014
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     05/29/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012028 Licensee Name: PATRICK N GILLESPIE
Firm: 003715 Firm Name: WATTS ELECTRICAL CORP
Firm Phone: 718-444-3583  Firm Address: 393 MOTHER GASTON BLVD BROOKLYN NY 11212 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $106.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 6 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JASON MC CANST
Owner Business Name: CHURCH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  SUB-PANEL
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    55  20    20               
Buildings Total 55  20    20                  
Total Units : 95 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/21/2014 Notice: C - CALL TO OFFICE 05/07/2014
Power Issued: 04/21/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B375956
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/12/2014 03/17/2014 CCH A (60) (14) Y
INSPECTION COMMENTS: CHECK IF FIXTURE GROUNDED
 
(2) 04/03/2014 04/07/2014 CCH N (35) (0) Y
INSPECTION COMMENTS: NO ACCESS FRONT LIGHT KO MISSING
 
(3) 04/16/2014 04/21/2014 CCH A R E (50) (6) Y
INSPECTION COMMENTS: N
 
(4) 04/28/2014 05/07/2014 PAT H X (40) (0) Y
INSPECTION COMMENTS: N
 
(5) 05/09/2014 05/13/2014 CJH N (0) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(6) 05/29/2014 06/03/2014 PAT C R (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B375956
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
LIGHT FIXTURES IN CEILING NOT SUPPORTED
RSLV 03/12/2014 03/12/2014 04/16/2014
 
002 (999) OTHER
MC CABLE NOT BONDED TO BOX WALL CEILING 250.146
RSLV 03/12/2014 03/12/2014 04/16/2014
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUNDING TERMINAL INSTALLED IN PANEL
RSLV 03/12/2014 03/12/2014 04/16/2014
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
OPEN BOXES IN CEILING
RSLV 03/12/2014 03/12/2014 04/16/2014
 
005 ( 19) DEFECTIVE WIRING IS IN USE
NO DIS SW ON FEEDERS
RSLV 03/12/2014 03/12/2014 04/16/2014
 
006 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
OUTLET NEAR BASEMENT DOOR NOT PROPERLY INSTALLED MC CABLE
RSLV 03/12/2014 03/12/2014 04/16/2014
 
007 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
FLOOR OUTLET NOT IN PROPER BOX
RSLV 03/12/2014 03/12/2014 04/16/2014
 
008 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
LIGHT FIXTURE IN CEILING NO SUPPORTED
RSLV 03/12/2014 03/12/2014 04/16/2014
 
009 (999) OTHER
MC CABLE NOT BONDED TO BOX WALL CEILING 250.146
RSLV 03/12/2014 03/12/2014 04/16/2014
 
010 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUNDING TERMINAL ISOLATED IN PANEL
RSLV 03/12/2014 03/12/2014 04/16/2014
 
011 ( 29) OUTLET BOXES ARE NOT COVERED
OPEN BOXES IN CEILING
RSLV 03/12/2014 03/12/2014 04/16/2014
 
012 ( 19) DEFECTIVE WIRING IS IN USE
NO DIS SW ON FEEDERS
RSLV 03/12/2014 03/12/2014 04/16/2014
 
013 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
OUTLET NEAR BSMT DOOR NOT PROPERLY INSTALL MC CABLE
RSLV 03/12/2014 03/12/2014 04/16/2014
 
014 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
FLOOR OUTLET NOT IN PROPER BOX
RSLV 03/12/2014 03/12/2014 04/16/2014
 
015 (999) OTHER
A 200 AMP DIS SW NEUTRAL IS BONDED 250.24A
RSLV 04/16/2014 04/28/2014 05/29/2014
 
016 ( 40) LOCKNUTS ARE MISSING OR LOOSE
200 AMP DIS NO LOCK NUT ON NIPPLE
RSLV 04/16/2014 04/28/2014 05/29/2014
 
017 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
200 AMP DIS EMT NOT PROPERLY INSTALL
RSLV 04/16/2014 04/28/2014 05/29/2014
 
018 (999) OTHER
B MC CABLE NOT BONDED TO OUTLET THROUGHOUT CEILING 250.146
RSLV 04/16/2014 04/28/2014 05/29/2014
 
019 (999) OTHER
C GROUNDING TERMINAL NOT PROPERLY INSTALL IN PANEL DRILL TAP 250.8.A
RSLV 04/16/2014 04/28/2014 05/29/2014
 
020 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
OUTSIDE BOX MISSING KO
RSLV 04/16/2014 04/28/2014 05/29/2014